Note the following with branch lines:
Maximum total length of the AS−Interface bus: 100 m
(without repeater/extender).
Length of cable for load voltage connection (depends
on the current consumption of the valve terminal and
the fluctuations in the load voltage).
Pin assignment Bus" (yellow cable):
1
Pin 2: AS−Interface + (brown)
2
Pin 1: AS−Interface − (light blue)
Pin assignment 24 V DC" (black cable):
3
Pin 1: 0 V (blue)
4
Pin 2: +24 V (brown)
Use cable sockets type ASI−SD−FK... from Festo for con
necting the valve terminal. You will then comply with
protection class IP65. Proceed as follows:
1. Press the AS−Interface cable into the upper part of the
cable socket.
2. Lay the cable free of stress.
3. Replace and screw tight the cable socket
(max. 0.3 Nm).
Seal open flat cable ends with cable cap type ASI−KK−FK or
cable sleeve type ASI−KT−FK from Festo. You will then avoid
leakage currents and comply with protection class IP65.
Festo CPV..−GE−ASI−8E8A−Z M8 0306c English