Technical Specifications - Bosch FLM-420-RLV1-E Guia De Instalacion

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
FLM-420-RLV1-E
Safety Notes
NOTICE!
Installation must only be performed by authorized and specialized personnel!
The connected device must have a minimum activation time of 20 ms.
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Functional description
The FLM-420-RLV1 Relay Interface Module Low Voltage has a change-over contact relay to provide a potential free
output contact.
The FLM-420-RLV1-E type in-built can be flush mounted in standard device boxes in accordance with EN 60670;
alternatively, it can be installed in the devices (see Figure 7 to Figure 8, Page 7).
Address setting
Address setting is carried out using the 8 DIP switches and a suitable pointed object (see Figure 1 to Figure 3, Page 4
and the following tables).
Address (A) Operating mode
0
Loop/stub in LSN improved version mode with automatic addressing
1 - 254
Loop/stub/T-taps in LSN improved version mode with manual addressing
255 = CL
Loop/stub in LSN classic mode (address range: max. 127)
Connection
Terminals
LSN: a1- | b1+ | a2- | b2+
LSN-POWER: 0 V | 0 V | +24 V | +24 V
LSN-SHIELD
REL1: COM | NO | NC
Figure 6 Page 7 shows the relay connected as
-
NO contact: continuous line
-
NC contact: dotted line.

Technical specifications

Relay
LSN input voltage
Max. current consumption from LSN
Contact load (resistive load)
-
Max. switched current and voltage
-
Min. switched current and voltage
-
Max. AC frequency
Minimum activation time of the connected device
Permissible wire diameter
Permissible operating temperature / storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions
Bosch Sicherheitssysteme GmbH
Function
LSN in / LSN out
LSN power supply (support points to loop through)
Cable shielding (if present)
Change-over relay (COM/NO contact/NC contact)
1 low voltage relay (NO/COM/NC)
15 to 33 V DC
1,75 mA
1 A / 30 V DC; 0.5 A / 42.4 V AC
0.01 mA / 10 mV DC; 0.01 mA / 10 mV AC
100 Hz
> 20 ms
2
0.6 to 2.0 mm
-20 °C to +55 °C / -25 °C to +80 °C
<96 %, non-condensing
IP 30
Class III equipment
ABS + PC blend, signal white (RAL 9003)
approx. 50 mm x 22 mm (Ø x H)
F.01U.013.004 | 7.0 | 2011.12
en
11
Tabla de contenido
loading

Tabla de contenido