CordSets and Receptacles
Use only high quality, well-insulated, grounded extension
cords with the generator's 120 Volt duplex receptacle.
Inspect extension cords before each use.
Checkthe ratings of all extension cords before you use
them. Extension cord sets used should be rated for 125 Volt
AC loads at 20 Amps or greater for most electrical devices.
Some devices, however, may not require this type of
extension cord. Checkthe operator's manuals of those
devices for the manufacturer's recommendations.
Keep extension cords as short as possible to minimize
voltage drop.
_k WARNING Overloadedelectrical cords can overheat,
arc, and burn resulting in death, bodily injury,
and/or property damage.
• ONLYusecordsratedfor your loads.
• Followall safetieson electrical c ords.
120/240 Volt AC, 50 Amp Receptacle
Use a NEIVIA 14-50 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volt AC loads at 50 Amps to
the plug.
Y (Hot)
240 Volts AC
RE7
"m
Frame Ground
AC -_
AC
W (Neutral)
NEMA 14-50
X (Hot)
This receptaclepowers 120/240 Volt AC, 60 Hz, single phase
loads requiring up to 10,000 watts of power (10.0 kW) at
41.6 Amps for 240 Volts or two independent 120 Volt loads.
The outlet is protected by a 2 pole GFCIcircuit breaker.
120/240 Volt AC, 30 Amp, LockingReceptacle
Use a NEIVIA L14-30 plug with this receptacle.Connecta
4-wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater). You can use the same 4-wire cord if you plan to run
a 120 Volt load.
4-Wire Cord Set
__11
20V 240V "_
W (Neutral)
Y (Hot)
|
X (Hot)
NEMA L14-30
/--/L 7 Ground (Green)
This receptaclepowers 120/240 Volt AC, 60 Hz, single phase
loads requiring up to 7,200 watts of power (7.2 kW) at
30 Amps for 240 Volts or two independent 120 Volt loads at
30 Amps each. The outlet is protected by a rocker switch
circuit breaker and/or a 2 pole GFCIcircuit breaker.
120 Volt AC, 30 Amp LockingReceptacle
Use a NEIVIAL5-30 plug with this receptacle. Connect a
3-wire cord set rated for 125 Volt AC loads at 30 Amps to
the plug.
®
®
II1111111
_'ireCord Set
NEMA L5-30
Neutral
120V
Hot
(Green)
Usethis receptacleto operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3,600 watts (3.6 kW) of power at
30 Amps. The outlet is protected by a rocker switch circuit
breaker and/or a 2 pole GFCIcircuit breaker.
NOTICE
Receptacles may be marked with rating value
greater than generator output capacity.
• NEVERattempt to power a device requiring more amperage than
generator or receptacle can supply.
• DO NOT overloadthe generator. SeeDon't OverloadGenerator.
13