Festo AS-Interface ASI-EVA Serie Manual De Instrucciones página 20

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
3.4 Connect sensors (PNP inputs)
In order to connect the sensors, use cables of type
KM12-DUO-... or sockets of type SEA-GS-7, SEA-M12-5GS-
PG7, SEA-GS-11-DUO or SEA-5GS-11-DUO. Fasten the plug
with the aid of the union nuts.
Seal unused sensor connections with protective caps of
type ISK-M 12. Only in this way can you comply with
protection class IP65.
Please note
– The inputs are based on IEC1131-2 type 02.
– The inputs are resistant to short circuits. In the event
of a short circuit, the slave will be switched off. The
AS-Interface master regards this slave as missing.
When the short circuit has been eliminated, the slave
indicates immediately that it can function again.
1
Pin assignment of the sensor
connection:
1: 24 V
2: Input In–2
3: 0 V
4: Input In-1
20
2
1
3
1
4
Festo ASI-EVA... 0208a English
Tabla de contenido
loading

Tabla de contenido