RS 34/1 MZ One-stage gas train
kW
1
MBC-DLE-120
MB 407 S2
(Rp 3/4")
(Rp 3/4")
70 0,6
5,2
75 0,6
5,6
100 1,0
8,2
125 1,4
11,1
150 2,4
15,7
11,0
175 3,5
21,1
14,4
200 4,6
27,2
18,1
225 5,8
33,9
22,1
250 6,9
41,3
26,4
275 8,0
49,4
31,3
300 9,1
58,0
36,6
325 10,2
67,2
42,2
350 11,3
76,7
47,8
375 12,4
86,7
53,7
390 13,1
57,4
RS 44/1 MZ One-stage gas train
kW
1
MB 407 S5
MB 410 S5
(Rp 3/4")
(Rp 1.1/4")
100
0,2
5,6
150
1,6
11,0
200
3,0
18,1
250
4,9
26,4
300
6,9
36,6
350
8,9
47,8
400 10,8
59,9
450 12,8
73,2
500 14,7
87,6
550 16,7
103,0
RS 34/1 MZ Two-stage gas train
kW
1
MB-ZR 407 S2
MB-ZR 410 S2
(Rp 3/4")
(Rp 1")
70 0,6
3,0
75 0,6
3,4
100 1,0
5,6
125 1,4
8,0
150 2,4
11,0
175 3,5
14,4
200 4,6
18,1
225 5,8
22,1
250 6,9
26,4
275 8,0
31,3
300 9,1
36,6
325 10,2
42,2
350 11,3
47,8
375 12,4
53,7
390 13,1
57,4
(A)
p (mbar)
2
MB 410 S2
MB 412 S2
(Rp 1.1/4")
(Rp 1.1/4")
3,0
--
--
3,4
2,1
--
5,6
2,9
--
8,0
4,2
2,1
5,6
2,8
7,2
3,6
9,0
4,5
11,0
5,5
13,2
6,5
15,5
7,6
18,0
8,7
20,5
9,9
22,9
11,2
25,4
12,7
27,0
13,5
p (mbar)
2
MB 412 S2
MB 415 S2
(Rp 1.1/4")
(Rp 1.1/2")
2,9
2,1
5,6
2,8
9,0
4,5
13,2
6,5
18,0
8,7
22,9
11,2
28,1
14,0
33,6
16,8
39,5
19,8
45,8
23,1
p (mbar)
2
MB-ZR 412 S2
MB-ZR 415 S2
(Rp 1.1/4")
(Rp 1.1/2")
2,1
2,1
2,1
2,1
2,9
2,1
4,2
2,1
5,6
2,8
7,2
3,6
9,0
4,5
11,0
5,5
13,2
6,5
15,5
7,6
18,0
8,7
20,5
9,9
22,9
11,2
25,4
12,7
27,0
13,5
MB 415 S2
MB 420 S2
(Rp 1.1/2")
(Rp 2")
--
--
--
--
--
--
--
--
--
--
--
--
--
--
3,2
--
3,3
--
3,8
--
4,3
--
4,8
3,2
5,4
3,4
5,9
3,8
6,3
4,0
MB 420 S2
(Rp 2")
3,2
3,2
3,2
3,2
3,2
3,2
3,3
3,2
4,3
3,2
5,4
3,4
6,5
4,1
7,7
4,9
9,0
5,7
10,2
6,6
MB-ZR 420 S2
(Rp 2")
--
--
--
--
--
--
--
--
--
--
--
--
--
--
3,2
--
3,3
--
3,8
--
4,3
--
4,8
3,2
5,4
3,4
5,9
3,8
6,3
4,0
6
GAS PRESSURE
The adjacent tables show minimum pressure
losses along the gas supply line depending on
the burner output.
Column 1
Pressure loss at combustion head.
Pressure of the gas at the socket 1)(B)p.7, with
combustion chamber at 0 mbar.
Column 2
Pressure loss of gas train 2)(B)p.7 includes: one
stage or two stage adjustment valve VR, safety
valve VS (both fully open), pressure governor R,
filter F.
The values shown in the various tables refer to:
natural gas G 20 PCI 9.45 kWh/Sm
3
(8.2 Mcal/Sm
)
With:
natural gas G 25 PCI 8.13 kWh/Sm
3
(7.0 Mcal/Sm
)
multiply the values of the table:
- column 1: by 1.5;
- column 2: by 1.35.
Calculate the approximate maximum output of
the burner in this way:
- subtract the combustion chamber pressure
from the gas pressure measured at test
point 1)(B)p.7.
- Find, in the table relating to the burner con-
cerned, the pressure value closest to the
result of the subtraction.
- Read the corresponding output on the left.
Example - RS 34/1/M MZ:
• Maximum output operation
• Natural gas G 20 PCI 9.45 kWh/Sm
• Gas pressure at test point 1)(B)p.7 =8.9 mbar
• Pressure in combustion chamber
An output of 250 kW shown in table RS 34/1
corresponds to 6.9 mbar pressure, column 1.
This value serves as a rough guide; the effective
delivery must be measured at the gas meter.
To calculate the required gas pressure at test
point 1)(B)p.7, set the output required from the
burner:
-
Find the nearest output value in the table for
the burner in question.
-
Read, on the right (column 1) the socket
pressure 1)(B)p.7.
-
Add this value to the estimated pressure in
the combustion chamber.
Example - RS 34/1 MZ:
• Required burner output: 250 kW
• Natural gas G 20 PCI 9.45 kWh/Sm
• Pressure of the gas at an output of 250 kW, from
the table RS 34/1 MZ, column 1
• Pressure in combustion chamber
6.9 + 2 =8.9 mbar
pressure required at test point 1)(B)p.7.
3
3
3
= 2 mbar
8.9 - 2 =6.9 mbar
3
=6.9 mbar
= 2 mbar