OWERING ON FROM THE
 Power the UPS by closing the SWIN input switch and leaving the SWMB maintenance switch open; if present, set the "1/0"
switch to "1".
After a few moments, the UPS is turned on, the capacitors are precharged and the "Lock / stand-by" LED blinks: The UPS is
in stand-by mode.
8
 Press the
button to access the power-on menu. When prompted to confirm, select "YES" and press the
All the LEDs around the display light up for about 1 sec. and a beep is emitted. The message "START UP" appears on the
display to inform the user of the beginning of the start up sequence which ends with transition of the UPS to load powered by
the inverter.
P
OWERING ON FROM THE
 If present, set the "1/0" switch to "1".
 Hold the "Cold Start" key down for about 5 seconds. The UPS will start and the display will light up.
8
 Press the
button to gain access to the power-on menu. When prompted to confirm, select "YES" and press the
All the LEDs around the display light up for about 1 sec. and the buzzer starts to beep once about every 7 seconds.
Note: if the sequence described above is not executed within 1 min., the UPS turns itself off to avoid discharging the batteries
unnecessarily.
P
OWERING OFF THE
From the main menu, select "OFF" and press
8
. To shut down the UPS completely, set the "1/0" switch (if present) to "0" and open the SWIN input switch.
Note: during prolonged periods of inactivity, it is good practice to shut down the UPS using the "1/0" switch (if
present); open the input and output switches and lastly, with the UPS off, open the battery fuse holders.