Several Battery Boxes can be connected in a cascade to ensure prolonged autonomy. The connections should be made as
shown here below:
WARNING (only for single UPS): No more than one UPS may be connected to each Battery Box or to more than one
Battery Box connected in a cascade.
S
R
ETTING THE
ATED
Having installed one or more BATTERY BOXES, the UPS must be set up to update the rated capacity value (total Ah of
batteries inside the UPS + external batteries).
To perform this operation, use the dedicated configuration software.
E
T
XTERNAL
EMPERATURE
This NON ISOLATED input may be used to measure the temperature inside a remote Battery Box.
The special kit provided by the manufacturers must be used: any methods not conforming to specifications may
cause faults or breakdowns in the equipment.
To install, connect the cable included in the special kit to the "EXT BATTERY TEMP PROBE" connector (see "View of the UPS
Connections" ref. 3).
After installation, enable the outdoor temperature measuring function using the configuration software.
R
EMOTE PANEL
The remote panel enables the remote monitoring of the UPS and gives a real time detailed summary of the machine status. The
device ensures that the operator can control the electrical values of the mains power, outputs, batteries, etc. and locate any
alarm conditions.
For further information regarding the connection and use of this device, please refer to its apposite manual.