4-2. GAS CHARGE
Perform gas charge to unit.
1) Connect gas cylinder to the service port of stop valve.
2) Perform air purge of the pipe (or hose) coming from refrigerant
gas cylinder.
3) Replenish
specified amount of the refrigerant,
while operating the air conditioner
for cooling.
Note:
In case of adding refrigerant, comply with the quantity specified for the refrigerating
cycle.
CAUTION:
When charging the refrigerant
system with additional
refrigerant,
be sure to use liquid refriger-
ant. Adding
gas refrigerant
may change
the composition
of the refrigerant
in the system and
affect normal operation
of the air conditioner. Also, charge the liquid refrigerant slowly, otherwise
the compressor
will be locked.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under
40°C (140°F)) during cold season. But never use naked fire or steam.
4-3. TEST RUN
Test runs of the indoor
units should
be performed
individually.
See the installation
manual
coming with the indoor unit, and make sure all the units operate properly.
If the test run with all the units is performed
at once, possible erroneous
connections
of the
refrigerant
pipes and the indoor/outdoor
unit connecting
wires cannot be detected.
Thus, be
sure to perform the test run one by one.
About
the restart
protective
mechanism
Once the compressor
stops, the restart preventive
device operates so the compressor
will not
operate for 3 minutes to protect the air conditioner.
Wiring/piping
correction
function
This unit has a wiring/piping
correction
function which corrects wiring and piping combination.
When there is possibility
of incorrect wiring and piping combination,
and confirming
the combi-
nation is difficult, use this function to detect and correct the combination
by following
the proce-
dures below.
Make sure that the following
is done.
Power is supplied
to the unit.
Stop valves are open.
Note:
During detection, the operation
of the indoor unit is controlled by the outdoor unit. During detec-
tion, the indoor unit automatically
stops operation.
This is not a malfunction.
Procedure
Press the piping/wiring
correction
switch (SW871)
1 minute or more after turning on the power
supply.
Correction
completes
in t0 to 15 minutes.
When
the correction
is completed,
its result is
shown by LED indication.
Details are described in the following table.
To cancel this function during its operation,
press the piping/wiring
correction
switch (SW87t)
again.
When the correction
completed
without error, do not press the piping/wiring
correction switch
(SW87t)
again.
When the result was "cannot
be corrected",
press the piping/wiring
correction
switch (SW871)
again to cancel this function.
Then, confirm the wiring and piping combination
in a conventional
manner by operating the indoor units one by one.
The operation is done while the power is supplied. Make sure not to contact parts other than
the switch, including the P.C. board. This may cause electric shock or burn by hot parts and
live parts around the switch. Contacting
the live parts may cause P.C. board damage.
To prevent electronic
control P.C. board damage,
make sure to perform static elimination
be-
fore operating this function.
This function does not operate when the outside temperature
is 0°C (32°F) or below.
I
I
I
Stop vatve
Union_
_
_
_
] n ] ] ¢" ] ] R ] IA
Indoor
Outdoor
L._ L_
L_
L_
unit
unit
Union_
_
[_
_
Stop valve with
Gas
Union _J U
_
_
service port
pipe
Refrig.... tgas
(_-_('_
_
cyfinder
\
-/k/
1'
I
4B36NA on y
operating valve
r_r-'---_r-lv,--_ - Gauge manifold
I
(for R410A),
_
valve (for R410A) I_
_
_u
I _hargehos e
L ._
J (forR410A)
_
Refrigerant gas cylinder for R410A with siphon
II
Refrigerant (liquid)
i H
'_'
_
Electronic scale for refrigerant charging
kj
o
co
(
r-q .... oB 8
D
D
_ D
LED indication
during
detection:
LED
1(Red)
t 2(Yellow)
t
3(Green)
Lighted
Lighted
Blinking
t (Red)
2 (Yellow)
3 (Green)
Lighted
Not lighted
Lighted
Blinking
Blinking
Blinking
Result of piping/wiring
correction
function
LED
Result
Completed
(Corrected successfully)
Cannot be corrected
Refer to "SAFETY
PRE-
CAUTIONS
WHEN LED
Other indications
FLASHES"
located behind
the service panel.
II
4-4. EXPLANATION
TO THE USER
Using the OPERATING
INSTRUCTIONS,
explain to the user how to use the air conditioner
(how to use the remote controller,
how to remove the air filters, how to
remove or put the remote controller
in the remote controller
holder, how to clean, precautions
for operation,
etc.).
Recommend
the user to read the OPERATING
INSTRUCTIONS
carefully.