Code
SA0051
The machine data for star connection were entered, the motor, however, is connected in delta. For
star operation, change the motor cable connection. For delta operation, check the entered rated
motor values.
Repeat the parameter identification
SA0052
The machine data for delta connection were entered, the motor, however, is connected in star. For
delta operation, change the motor cable connection. For star operation, check the entered rated
motor values.
Repeat the parameter identification
SA0053
A phase asymmetry was measured. Check the cables at the terminals of the motor and the frequency
inverter for proper connection and check the contacts for corrosion.
GB
SA054
The Resolver angle was not estimated correctly.
Code
No error message exists
SF000
SF001
The value entered for parameter
SF002
The value for parameter
376 and
SF003
The value entered for parameter
rect the value.
SF004
The calculated slip frequency is negative. Correct the values entered for parameters
and
Rated Frequency
SF005
The calculated slip frequency is too high. Correct the values entered for parameters
and
Rated Frequency
SF006
The calculated total output of the drive is lower than the rated power. Correct the value entered for
parameter
SF007
The set configuration is not supported by the guided commissioning. In this document, Configurations
110 and 410 are described. Select one of these configurations for parameter
Code
SF0011
The main or leakage inductance measurement has failed because the motor has a high slip. Correct
SF0012
the rated motor values in parameters 370, 371, 372, 374, 375 and 376. Carry out the guided
commissioning once again. In case an error message is displayed again for parameter
30, enter value 110 (sensor-less control according to U/f characteristic) if value 410 was set so far.
Carry out the guided commissioning once again.
SF0021
The measurement of the stator or rotor resistance did not deliver a plausible value. Check the cables
SF0022
at the terminals of the motor and the frequency inverter for proper connection and check the contacts
for corrosion and safe contact. Repeat the parameter identification
SF026
The setup-routine is aborted.
72
Warning messages after guided commissioning
Error messages during guided commissioning
Rated Current
Rated Current
370. Correct the values.
Rated Voltage
Rated Cos phi
375.
375.
376.
Rated power
Error messages after guided commissioning
Meaning / Measure
Meaning / Measure
371 is too low. Correct the value.
371 is too high referred to parameters
374 is incorrect (greater than 1 or less than 0.3). Cor-
Meaning / Measure
Quick Start Guide ACU
Rated Power
372
Rated Speed
372
Rated Speed
30.
Configuration
Configuration
02/15