FUNCTION
Bypass frequency tolerance
Bypass min.-max. threshold
Eco mode sensibility
Eco mode
min.-max. threshold
UPS without battery
Battery low time
Automatic battery test
Parallel common battery
Internal battery capacity
External battery capacity
Battery charging algorithm
Battery recharging current
DESCRIPTION
Selects the accepted range for the input frequency for
switching to the bypass and for the synchronisation of
the output
Selects the accepted voltage range for switching to
the bypass
Selects the intervention sensitivity during operation in
ECO mode
Selects the accepted voltage range for operation in
ECO mode
Operating mode without batteries (for converters or
voltage stabilizers)
Estimated autonomy time remaining for "battery low"
warning
Interval of time for the automatic battery test
Common Battery for parallel UPS systems
Nominal Battery capacity for internal batteries
Nominal Battery capacity for external batteries
Algorithm and Battery recharging threshold
Recharging current compare to battery nominal
capacity
- 91 -
DEFAULT
± 5%
Low: 180V
High: 264V
Normal
Low: 200V
High: 253V
Operating with Batteries
3 min.
40 ore
Disable
Change according with
UPS model
7Ah for UPS without
internal batteries;
0Ah all other cases
Two levels
12%