If the output voltage is set to 200V and 208V (see "Configuring the UPS" paragraph), the maximum power output of the
UPS is reduced with respect to its rated value, as shown in the graph below:
C
ONFIGURING THE
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
Language*
Output voltage
Buzzer
Operating mode**
Battery low **
Date and time**
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.
L
(
200V
OAD
TO
UPS
DESCRIPTION
Selects mimic panel
language language
Selects the rated output
voltage
(Phase - Neutral)
Selects the audible alarm
operating mode
Selects one of five different
operating modes
Estimated autonomy time
remaining for "battery low"
warning
UPS internal watch setup
208V)

AND

DEFAULT
 English
 Italian
English
 German
 French
 220V
 230V
230V
 240V
 Normal
 Reduced: does not sound due to the
Reduced
momentary intervention of the bypass
 ON LINE
 ECO
ON LINE
 SMART ACTIVE
 STAND-BY OFF
 1 ÷ 7 @1 min step
3 min.
- 89 -
POSSIBLE CONFIGURATIONS
 Spanish
 Polish
 Russian
 Chinese