Configurations which can be modified by means of configuration software available at service centres are listed in the
following table.
FUNCTION
Operating mode
Output voltage
Output nominal frequency
Autorestart
Auto power off
Buzzer Reduced
EnergyShare off
Autonomy limitation
Maximum load
Bypass Synchronization
speed
External synchronization
External temperature
Bypass mode
Bypass active in stand-by
DESCRIPTION
Selects one of five different operating modes
Selects the rated output voltage
(Phase - Neutral)
Selects the rated output frequency
Waiting time for automatic power-on after the return of
mains voltage
Automatic UPS power-off in battery operation mode if
the charge is lower than 5%
Selects the audible alarm operating mode
Selects the auxiliary socket operating mode
Maximum battery operation time
Selects the user overload limit
Selects the synchronisation speed of the inverter to
the bypass line
Selects the source of synchronisation for the inverter
output
Activates reading of the external temperature probe
Selects the mode of use of the bypass line
Load supply from bypass with UPS in stand-by
- 90 -
DEFAULT
ON LINE
230V
50Hz
5 sec.
Disabled
Reduced
Always connected
Disabled
Disabled
1 Hz/sec
From bypass line
Disable
Enabled /
High sensitivity
Disable (load NOT
supplied)