Technical Specifications; Electrical Specifications - Leviton 1000 Serie Manual De Instalación

Ocultar thumbs Ver también para 1000 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

2
TECHNICAL SPECIFICATIONS
2.1
Electrical Specifications
Series 1000 and Series 2000 Meters fall under UL Circuit Category III: a device for
measurements performed in the building installation. The electrical and
environmental specifications for Series 1000 and Series 2000 meters are given in
Table 1 and Table 2 below:
Input Configurations
Supply Voltage Range (Line to
Neutral)
Maximum Input Power
Maximum Rated Current
Line Frequency
Power Factor Range
Accuracy
1
Meter Operating Temperature
Display Operating Temperature
Rated Pollution Degree
2
Rate Relative Humidity
Terminal Block Torque Ratings:
Voltage Terminal
CT and I/O Terminal
Accuracy based on Leviton solid core current transformers (included), with 100 mA secondary output.
1
Meter input burden resistance at 2 Ohms
2
Pollution Degree 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary
conductivity caused by condensation must be expected.
Series 1000 Electrical Specifications
1 Phase, 2 Wire (120V or 277V)
102-138VAC
235-320VAC
7VA
Primary: Max Operating Current
+ 10%
Secondary: 0.12A
50-60Hz
0.5 to 1.0 Leading or Lagging
+/- 0.5% of registration @ 1.0 PF,
1% to 100% of rated current
+/- 0.75% of registration @ 0.5
PF, 1% to 100% of rated current
-30 to 60° C
-20 to 50° C
2
80%
12 in-lb max
4.4 in-lb max
Table 1 - Series 1000 Electrical Specifications
7
1 or 2 Phase, 3 Wire (120/208V,
120/240V, or 277/480V)
102-138VAC
235-320VAC
7VA
Primary: Max Operating Current
+ 10%
Secondary: 0.12A
50-60Hz
0.5 to 1.0 Leading or Lagging
+/- 0.5% of registration @ 1.0 PF,
1% to 100% of rated current
+/- 0.75% of registration @ 0.5
PF, 1% to 100% of rated current
-30 to 60° C
-20 to 50° C
2
80%
12 in-lb max
4.4 in-lb max
Tabla de contenido
loading

Este manual también es adecuado para:

2000 serie

Tabla de contenido