Fitting the Terminal Blocks
To insert the terminal blocks into the unit use the following method:
1 Insert a corner of the block into the slot (see a).
2 Push the length of the block into the slot until the block 'clicks'
into place, the 2 upper hooks on the block should be visible
(see c).
a
Table 2: Wiring Terminal Designations
(Note - Terminals marked CH2 will only be available on 2 channel
models)
No.
Function
1
Ext Power In +
2
Ext Power In -
3
Aux Power In +
4
Aux Power In -
5
NC Alarm Relay
6
C Alarm Relay
7
NO Alarm Relay
8
NC Alarm Relay
9
C Alarm Relay
10
NO Alarm Relay
11
NC Fault Relay
12
C Fault Relay
13
NO Fault Relay
14
NC Fault Relay (AUX)
15
C Fault Relay (AUX)
16
NO Fault Relay (AUX)
17
Sounder Output 1 -
18
Sounder Output 1 +
19
Sounder Output 2 -
20
Sounder Output 2 +
21
Configurable Input +
22
Configurable Input -
23
Not Used
24
Loop out -
25
Loop switched out +
26
Loop in -
27
Loop in +
28
Loop not switched out +
Table 3: Relays
RELAY
ALARM 1 or 2
FAULT 1 or 2
SOUNDER 1 or 2
Table 3a: Relay Electrical Specification
SPECIFICATION
MIN
Contact Rating
Life Time
10
5
N200-102-00
b
Primary PSU
Primary PSU
Not used in default
Not used in default
CH1
CH1
CH1
CH2
CH2
CH2
CH1
CH1
CH1
CH2
CH2
CH2
47 k-ohm EOL Resistor
47 k-ohm EOL Resistor
(Reset)
Default is active = short circuit
(Reset)
(unsupervised)
To use isolator
Internally connected to 27
ACTION:
Controlled by panel when it determines
alarm condition has been met.
When FAULT CONDITION on Ch1 or Ch2
or a common FAULT occurs. Fault is also
signalled when in Service Mode and when
the device is unpowered.
Set ON when a channel is in ALARM.
Sounder 1 corresponds to Ch1 and
Sounder 2 corresponds to Ch2
MAX
UNITS
COMMENTS
2
A
30 VDC resistive load
0.5
A
30 VAC resistive load
Operations
WARNING: Switching Inductive Loads
FAAST LT
c
FAAST LT
FAAST LT
T1
T2
T3
T4
nductive loads can cause switching surges, which may
I
damage the module relay contacts (see above).
T5
To protect the relay contacts, connect a suitable Transient
Voltage Suppressor (for example 1N6284CA ) across the
T6
load as shown.
T7
Alternatively, for unsupervised DC applications, fit a diode
with a reverse breakdown voltage greater than 10 times the
T8
circuit voltage.
T9
T10
NOTES
Set ON and OFF by panel; not latched
Fault state is not latched.
Default condition = set on in ALARM.
5
~
1N6284CA
P
R
r
L
C
P
L/C
I56-3947-202