THE ELECTRONIC CIRCULATOR
Electronic control of operation:
a) Control mode p – c
In this mode, the electronic controller keeps the differential
pressure generated by the pump at a constant set value of H s.
Pressure differential
b) Control mode p – v
In this mode, the electronic controller varies the pressure
differential between the set value Hs and 1/2 H s. The pressure
differential varies with the volume fl ow.
Pressure differential
LED
MEANING
Green led on
Working pump
The green led
fl ash quickly
The led fl ash
The pump is ready to
with light red/
work but doesn't turn
green
The led fl ash
Pump out of service
with red light
Led off
No supply voltage
INSTRUCTIONS FOR USE
Volume fl ow
Volume fl ow
WORK CONDITION
The pump works in base of its
settings
The pump works 10 minutes to
purge the air. After it is neces-
sary to set the power
The pump will start to work
automatically when the pro-
blem is solved
The pump is stopped (blocked) The pump doesn't start automa-
The pump doesn't receive the
voltage
c) Venting procedure
This procedure allows the expulsion of air present in the
hydraulic circuit. After manual selection of the "AIR" mode,
the pump will automatically alternate between maximum and
minimum speed for 10 minutes. At the end of the procedure,
the circulator will go to the pre-set speed. You can then select
the desired mode of operation
CAUSE
Normally work
Normally work
- undervoltage U < 160V
overvoltage U > 253V
- Engine temperature too high
tically
- The pump isn't connected on
the motherboard
- The led is defective
- The pump is defective
- 37
-
RESOLUTIVE ACTION
- Check the voltage
195V < U < 253V
- Check the water temperature
Change the pump
- Check the wire connection
- Check if the pump works
- Change the pump