GRE HPG25 Manual De Instrucciones página 9

Bombas de calor para piscinas sobre suelo y enterradas
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
refrigerant. Make sure that the correct number of cylinders are provided for recovering all of the refrigerant. All cylinders
used must be intended for the recovery of refrigerant and must be labelled for this specific refrigerant. The cylinders must
be equipped with a vacuum valve and a stop gate in good working order. Empty collection cylinders are drained and, where
possible, cooled before recovery.
 The recovery equipment must be in good working order, the instructions for using the equipment must be within reach
and the equipment must be compatible for use with the refrigerant concerned, including, where appropriate, a flammable
refrigerant. Moreover, a set of calibrated scales must be available and in good working order. The pipework must be
complete, have no leaks or disconnected connectors, and must be in good condition. Before using the recovery unit, check
that it is in good working order, that it has been well maintained and that the associated electric components are sealed so
as to prevent any risk of fire in the event of refrigerant being released. If you have any doubts, contact the manufacturer.
 The recovered refrigerant must be sent to the refrigerant supplier in its recovery cylinder with a waste transfer note. Do
not mix different refrigerants in the recovery units, and in particular in the cylinders.
 If the compressor has been removed or if oil from the compressor has been drained, check that the refrigerant has been
completely removed to prevent it from mixing with the lubricant. The draining process must be carried out before
returning the compressor to the supplier. Only the electric heater of the compressor body can be used to accelerate this
process. This operation can be carried out safely once all liquids within the system have been drained.
RECYCLING
This symbol is required by the European directive DEEE 2012/19/EU (directive on
waste electrical and electronic equipment) and means that your appliance must not
be thrown into a normal bin. It will be selectively collected for the purpose of reuse,
recycling or transformation. If it contains any substances that may be harmful to the
environment, these will be eliminated or neutralised. Contact your retailer for
recycling information.
6

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Hpg40Hpg50Hpg70

Tabla de contenido