7
Technical data
Controller
•
CE marking:
•
Low voltage tests: EN 60730-1* and EN 60730-2-1**
•
Electromagnetic compatibility (EMC) tests: EN 60730-1
and EN 301-489-3
•
Power supply: 230 V AC +10/-15 %, 50 Hz
•
Isolation: IP20
•
Storage temperature: -20 °C to +70 °C
•
Operating temperature: 0 °C to +55 °C
•
Ambient relative humidity (RH): < 95 % at 20 °C
•
Power consumption:
•
< 90 W in full charge
•
< 2 W without any charge
•
Pump and boiler relay outputs:
•
230 V AC +10 %/-15 %
•
< 250 VA
•
Only dry contact
•
Heating–cooling and dew-point inputs: Only dry contact
•
Actuator outputs:
•
24 V DC ±5 %, 218 mA maximum per output 3 to 12
•
24 V DC ±5 %, 436 mA maximum per output 1 and 2
•
Dew-point sensor module output:
•
24 V DC ±5 %, 40 mA maximum
•
Supply connection: wires 1.5 mm² maximum
•
Pump and boiler connection: wires 1.5 mm² maximum
*) EN 60730-1 Automatic electrical controls for household and
similar use, Part 1: General requirements
**) EN 60730-2-1 Automatic electrical controls for household
and similar use, Part 2-1: Particular requirements for electrical
controls for electrical household appliances
***) EN 60730-2-9 Automatic electrical controls for household
and similar use, Part 2-9: Particular requirements for temperature
sensing controls
Cables
The following table specifies cables to be used guaranteed without EMC problems:
Cable
C-33/C-35 to actuator
C-33/C-35 to thermostat
Thermostat to external sensor
Thermostat to floor sensor
C-33/C-35 to heating/cooling relay
C-33/C-35 to timer
C-33/C-35 to dew-point sensor module
10
Thermostats and Timer
•
CE marking:
•
Low voltage tests: EN 60730-1* and EN 60730-2-9***
•
EMC tests: EN 60730-1 and EN 301-489-3
•
Power supply: +6 to +12 V DC through wires from controller
•
Isolation:
•
T-33, T-35, T-37: IP20
•
T-34, T-36, T-38, I-36: IP31
•
Operating temperature:
•
T-33, T-35, T-37: 0 °C to 50 °C
•
T-34, T-36, T-38, I-36: 0 °C to 40 °C
•
Storage temperature:
•
T-33, T-35, T-37: -20 °C to +70 °C
•
T-34, T-36, T-38, I-36: -10 °C to +60 °C
•
Ambient relative humidity (RH):
•
T-33, T-35, T-37: < 95 % at 20 °C
•
T-34, T-36, T-38, I-36: < 85 %
•
Consumption: < 5 mA
•
All thermostats: < 5 mA
•
Timer I-36: < 15 mA
•
Backup time, T-38 and I-36 only: 2 h
•
Wire thermostat to controller: 2×0.5 mm
•
Wire thermostat to floor sensor: < 4 m
Standard cable length
Maximum cable length
0.75 m
2 m
—
50 m
5 m
5 m
4 m
4 m
—
20 m
—
5 m
—
20 m
2
, < 50 m
Wire gauge
0.2 – 1.5 mm
2
2×0.5 mm
2
0.6 mm
2
0.75 mm
0.2 – 1.5 mm
0.2 – 1.5 mm
0.2 – 1.5 mm
UPONOR CONTROL SYSTEM WIRED - QUICK GUIDE
2
2
2
2