Digital Inputs; Operating Conditions; Electromagnetic Compatibility - LEGRAND IME CONTO D4-Pt Manual De Instalación

Ocultar thumbs Ver también para IME CONTO D4-Pt:
Tabla de contenido
• Technical characteristics

Digital inputs

Voltage:
Current:
Pulse output
Type:
Voltage:
Current:

Operating conditions

Operating temperature:
Storage temperature:
Humidity:
Max. dissipated power:
Mechanical environment:
Electromagnetic environment:
Relative humidity:
Installation:
Use:
CE Marking
The CE4TB0PCL1 - CE4TBDTCL1 - CE4TBMTCL1- CE4TB0PMID - CE4TBDTMID - CE4TBMTMID devices comply with:
• The requirements of the European directive on electromagnetic compatibility (EMC) n° 2014/32/EU
• The low voltage directive n° 2014/35/UE.
• Directive 2011/65/EU modified by directive 2015/863 (RoHS 2).

Electromagnetic compatibility

According to IEC/EN 62052-11; EN 50470-1; EN 62053-21 and EN 50470-3
Insulation (IEC/EN 62052-11, IEC/EN 62053-21)
Measurement category:
Degree of pollution:
Insulation voltage, Ui:
Impulse withstand voltage
Front surface:
30
12-24V DC
Max. 10 mA
Optorelays with potential-free SPST-NO contact
Max. 27 V AC/DC
Max. 50 mA
(-25°C) ÷ (55°C) [-13°F ÷ 131°F]
(-25°C) ÷ (70°C) [-13°F ÷ 158°F]
Suitable for tropical climates
≤ 10 W
M1
E2
95% not condensing (EN50472-1)
Mounting the KWH-meter in a IP51 switchboard
Indoor
III
2
300V Phase-Earth
- Measuring inputs / Digital I/O inputs
wave 1,2 / 50μs 0,5 J: 6kV
alternate voltage 50Hz / 1 min.: 4kV
- All circuits / earth
alternate voltage 50Hz / 1 min.: 4kV
Class II