IO-Link Data Dictionary
21.10.01.00065/02
Diagnostic Buffer - Details
Data Format of Single Entry (ISDU 132)
Bytes 0...1
Bytes 2...5
Diagnostic-Type (MSB first)
Counter cc1 (MSB first)
Data Format of Diagnostic Buffer (ISDU 131)
Bytes 0...5
Bytes 6...11
Bytes 12...17
Entry 1 (newest)
Entry 2
Entry 3
Encoding of Diagnostic-Type
Diagnostic-Type
Description
Notifications
0x1401
Notification: Device powered on
0x1402
Notification: Diagnostic buffer cleared
0x1403
Notification: Parameters restored to factory defaults
0x1404
Notification: Vacuum sensor calibrated successfully
0x1405
Notification: Manual mode entered
0x0405
Notification: Manual mode exited
0x14AA
Notification: Corrupted entry
Errors
0x1201
Error E01: Internal Error
0x1202
Error E02: Internal Error
0x1203
Error E03: Vacuum sensor calibration failed
0x1207
Error E07 appeared: Primary voltage US too low
0x0207
Error E07 disappeared: Primary voltage US too low
0x1208
Error E08 appeared: IO-Link communication interrupted
J. Schmalz GmbH
...
Bytes 223...228
...
Entry 38 (oldest)
9 of 11
SCPSi series
J. Schmalz GmbH
Aacher Straße 29, D 72293 Glatten
Tel.: +49(0)7443/2403-0
Fax: +49(0)7443/2403-259
Remark
Counter value cc1 of when the entry was recorded
Remark
Buffer of 38 entries (newest to oldest) with encoding as in ISDU 131
Remark
Single entry was written incorrectly - do not evaluate
Remains until next power-on
Remains until next power-on
29.08.2014
SCPSi Data Dictionary