Honeywell Panel EnviraZone W8835 Manual Del Usuario página 5

Ocultar thumbs Ver también para Panel EnviraZone W8835:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Wiring Thermostats
Run wire from the VisionPRO® IAQ Thermostat 1, 2, 3
terminals to the corresponding terminals on any one of the
EnviraCom bus terminal sets. More than one thermostat can
be connected to a bus terminal. See Fig. 3.
Wiring Equipment
CONVENTIONAL EQUIPMENT
Connect the first stage heat to W1/E, second stage heat to W2,
and third stage heat to W3/Aux. Wire first stage cooling to Y1,
and second stage cooling to Y2. See Fig. 3.
SINGLE TRANSFORMER
HEATING/COOLING SYSTEMS
REQUIRE A JUMPER TO BE
INSTALLED CONNECTING RH
AND RC (FACTORY INSTALLED).
R
W1
W2
DOTTED LINES FOR 2-
STAGE APPLICATIONS
Y1
Y2
G
C
EARD-6
POWER-CLOSED/
SPRING-OPEN
ZD DAMPER
L
HEAT
COOL
PURGE
FAN
C
RH
RC
W1/E
W2
W3/AUX
LED STATES:
Y1
Heat LED
Heating Mode
Cool LED
Cooling Mode
Y2
Purge LED
Purge Mode
Fan LED
Fan Mode
G
Em Heat LED Em Heat Mode
COMM LED
Communications
O/B
DIP SWITCH SETTINGS
HUM
1 SEE TABLE
ON
2 SEE TABLE
1
HUM
3 ENVIRACOM FURN
NO
4 PURGE TIME
2 MIN
DEHUM
5 PURGE FAN
HVAC
6 PURGE DAMPER
NO CHG
DEHUM
7 # COMP STAGES
1
8 HEAT FAN
HVAC
VENT
9 HP CHANGEOVER
O
10 UNUSED
VENT
DAMPERS
ZONE1
ZONE2
ZONE3
M6 M4 M1
M6 M4 M1
M6 M4 M1
POWER-CLOSED/
SPRING-OPEN
ZD DAMPER
1
2
POWER-CLOSED/
SPRING-OPEN
ARD DAMPER
VISIONPRO IAQ
Fig. 3. Conventional equipment wiring diagram.
5
If separate HVAC equipment transformers are used for the
heating and cooling systems, such as for an oil furnace, wire
the heating transformer hot wire to Rh and the cooling
transformer hot wire to Rc. Locate the Rh/Rc jumper above the
equipment terminals and remove the jumper to expose the two
pins.
HEAT PUMP EQUIPMENT
Connect the Y1 terminal to the first stage compressor, and the
Y2 terminal to the second stage compressor. W3/Aux is the
auxiliary heat and W1/E is the emergency heat. If emergency
heat and auxiliary heat use the same piece of equipment,
place a jumper from W3/Aux to W1/E and wire it to the resistive
heat equipment. See Fig. 4 and 5. See Fig. 6 and 7 for two-
stage heat pump equipment.
EM HEAT
COM
ZONE 1
ZONE 2
W8835
A
REMOVE JUMPERS IF
T1 AND T2 ARE USED
ZONE LEDS:
On
Damper open or opening
Off
Damper closed or closing
MOMENTARY PUSH BUTTONS
Boot
Clears Microprocessor
Purge Override Bypass Purge Mode
Discovery
Initiates Discovery Mode
O
OFF
N
0
1 2 3 4 5 6 7 8 9 10
YES
3.5 MIN
PANEL
#1
#2 CONV HT STG
OPEN
1
1
1
2
1
0
2
PANEL
0
1
3
B
0
0
HP
ENVIRACOM BUS
1 2 3
1 2 3
1 2 3
1
2
3
3
VISIONPRO IAQ
W8835 ENVIRAZONE PANEL
ZONE 3
ENVIRACOM
XFRM
L1
R
R
C
C
L2
T1
24 VOLT/40 VA
T2
TRANSFORMER
DAMPER
XFRM
1 2 3
1
2
3
C7835A DISCHARGE
AIR SENSOR
1
2
3
VISIONPRO IAQ
M23674
68-0258ES—3