NV Media Card parameter
187
C.tyP
set not compatible with cur-
rent drive mode
NV Media Card file/data is
188
C.cPR
different to the one in the
drive
189
OI.A1
Analog input 1 over-current
190-
rES
Spare
198
Two or more parameters are
199
dESt
writing to the same destina-
tion parameter.
Option module 1 hardware
200
SL.HF
fault
Option module watchdog
201
SL.To
function service error
Option module in option slot 1
202
SL.Er
has detected a fault
Option module in option slot 1
203
SL.Nf
has been removed
Option module in option slot 1
204
SL.dF
has changed
205-
rES
Spare
214
Option module does not
215
OPt.d
acknowledge during drive
mode changeover
217-
rES
Spare
216
218
tH.Fb
Internal thermistor has failed
Control stage over-tempera-
219
Oht.c
ture
Power system configuration
220
P.dAt
data error
Hardware trip has occurred
221
St.HF
during last power down
222-
rES
Spare
224
225
Cur.O
Current feedback offset error
Indice de revisión : E - Julio de 2017
Current input on analog input 1 exceeds 24mA.
• Set Pr mm.000 to 'Destinations' or 12001 and
check all visible parameters in all menus for param-
eter write conflicts
• Ensure the option module is installed correctly
• Replace the option module
• Replace the drive
• Replace the option module
• Ensure the option module is installed correctly.
• Re-install the option module.
• To confirm that the removed option module is no
longer required perform a save function in Pr
mm.000.
• Turn off the power, ensure the correct option
module is installed in the option slot and re-apply
the power.
• Confirm that the currently installed option module
is correct, ensure option module parameters are
set correctly and
perform a user save in Pr mm.000.
Hardware fault – Contact the supplier of the drive
This trip indicates that a control stage over-temper-
ature has been detected if Cooling Fan control
(06.045) = 0.
Increase ventilation by setting Cooling Fan control
(06.045) > 0.
Hardware fault – Contact the supplier of the drive
Enter 1299 in Pr mm.000 and press reset to clear the
trip
The current offset is too large to be trimmed.
• Ensure that there is no possibility of current flowing
in the output phases of the drive when the drive is
not enabled
• Hardware fault – Contact the supplier of the drive
45