Status Messages - ABB DCS 600 MultiDrive Guía Rápida De Inicio

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

8 Status messages

Categories of mes-
sages and display
options
General messages General messages will only be indicated on the seven - segment
SDCS-CON-x
SDCS-AMC-DC x
Power-up error (E) Power-up errors will only be indicated on the seven - segment dis-
SDCS-CON-x
Fault messages (F) Fault messages are indicated on the seven - segment display of the
taken from/for further information:
Operating instructions
3ADW000080
The thyristor power converters series DCS 600 MultiDrive genera-
te general messages, power - up errors, fault and alarm messages.
The messages are indicated on the seven - segment display of the
SDCS-CON-x processor board or by means of a red LED on the
SDCS-AMC-DC x board. On the seven - segment display the mes-
sages appear in code. The letters and numbers of multi - character
codes are displayed one after the other for 0.7 seconds at a time.
Plain text messages are available on the control and display panel
(CDP 31x) and in the fault logger of DriveWindow.
display / LEDs of the SDCS-CON-x / SDCS-AMC-DC x boards.
8
SDCS-CON-x firmware is not running
.
SDCS-CON-x firmware running, no faults, no alarms
L
Indication while loading firmware into SDCS-CON-x
(1) Units should be deenergised and energised. If the fault occurs again check
the SDCS-POW-x and the SDCS-CON-x boards and change them if necessa-
ry.
LED
green
SDCS-AMC-DC x firmware is running
red
Fault; see panel and DriveWindow
play of the SDCS-CON-x boards. With a power-up error active it is
not possible to start the drive.
E1
SDCS-CON-x ROM memory test error
E2
SDCS-CON-x RAM memory test error
E5
SDCS-CON-x no firmware in memory
E6
SDCS-CON-x hardware is not compatible
(1) Units should be deenergised and energised. If the fault occurs again check the
SDCS-POW-x and the SDCS-CON-x boards and change them if necessary.
(2) Load firmware.
SDCS-CON-x processor board or by means of a red LED on the
SDCS-AMC-DC x board. On the seven - segment display the mes-
sages appear in code (Fxx). The letters and numbers of multi - cha-
racter codes are displayed one after the other for 0.7 seconds at a
time. Plain text messages are available on the control and display
panel (CDP 31x) and in the fault logger of DriveWindow.
All fault messages, with the exception of F17, F18, F20 and F44,
are resetable in case the fault is eliminated.
To reset a fault following steps are required:
- remove the RUN and ON commands
- eliminate the faults
- acknowledge the fault with RESET via digital input, overriding
control system or in 'LOCAL' mode with the panel and Drive-
Window
- depending on the systems condition, generate ON and RUN
commands again
The fault signals will switch the drive off completely or partly.
3ADW000179R0100_DCS600_QuickGuide_edisf_a
Description
Description
Description
Remark
(1)
Remark
Remark
(1)
(1)
(2)
(1)