ICAR by ORTEA NEXT
4.3
AUT
MODE
In automatic mode, the controller calculates the optimum configuration of capacitor steps in order to reach the set cos.
The selection criteria takes into account many variables such as: the power of each step, the number of operations, the total
time of use, the reconnection time, etc. The controller displays the imminent connection or disconnection of the steps with
the flashing of their identification number (left). The flashing can last in cases in which the insertion of a step is not possible
due to the reconnection time (discharge time of the capacitor). The device initiates automatic corrections when there is an
average reactive power request (kvar) higher than 50% of the smallest step, and the measured cos is different from the
setpoint.
5
MEASURES
The RPC 5LGA controller provides a set of measurements displayed on the alphanumeric display, in conjunction with the
current cos that is always displayed on the main display. Press the
After 30 seconds without pressing any buttons, the display automatically returns to the default measurement defined by
P.47. If P.47 is set on the ROT, then the measures rotate automatically every 5 seconds. At the bottom of the list of measures
it is possible to set the setpoint of the cos, acting on the same value set with P.19. Below is a table with the measurements
displayed.
M
EASURE
D
-kvar
ELTA
▼
▲
V
OLTAGE
▼
C
URRENT
▼
A
PF
VERAGE
▼
THD
.
CAP
▼
T
EMPERATURE
▼
V
THD
OLTAGE
▼▲
VH02... ...VH15
C
THD
URRENT
▼▲
IH02... ...IH15
COS
SETPOINT
▼▲
S
TEP POWER
▼▲
S
TEP COUNTER
▼▲
S
TEP HOURS
▼▲
These measures are shown only if the Step trimming function is enabled (P.25=ON) and the advanced password is
enabled and entered.
MAN mode
icon
Tot kvar inserted in
MAN
▲▼: Select step -
I
D
CON
ESCRIPTION
kvars needed to reach the cosphi setpoint. If delta-kvar is positive cpacitors need to be
Δkvar
inserted, if negative to be disconnected.
kvar
Total kvar of the plant.
ΔSTEP
Number of equal steps to achieve the target power factor.
V
RMS voltage of the plant current.
V HI
Maximum voltage value measured.
A
RMS current of the plant voltage.
A HI
Maximum current value masured.
WPF
Weekly average power factor.
PF
Instantaneous total power factor.
THdC
Capacitors total harmonic distortion (THD) in current.
TC HI
Maximum THD value measured.
°C °F
Temperature of internal sensor.
°CHI °FHI
Maximum temperature value measured.
THDV
Total harmonic distortion % (THD) of plant voltage.
% voltage harmonic content from 2.nd up to 15.th order
THDI
Total harmonic distortion % (THD) of plant current.
% Current harmonic content from 2.nd up to 15.th order
IND CAP
Setting of desired cos setpoint (same as P.19).
%
Step residual power, as a percentage of the set rated power.
OPC
Operation counter of the step.
H
Hour meter of the step insertion.
Connected
steps
Manual step
selection
:Change step status
key to scroll through the measures in rotation.
12 / 40