Configuración Del Número De Grupo; Configuración Del Número De Grupo De Unidades Interiores - LG ARUB Serie Manual De Instalación

Ocultar thumbs Ver también para ARUB Serie:
Tabla de contenido
PCB de la unidad RC
Setting method of Master indoor unit in zoning
1) Turn dip switch 5,6,10 on at system off.
2) Set the left Ratary switch for HR unit.(Rotary switch No. "0" ➔ HR unit No. "1")
3) Set the right Ratary switch for IDU unit.(Rotary switch No. "0" ➔ HR unit branch No. "1")
4) Display the Master IDU No. of the HR unit on 7segment.(Default display is "00" on 7segment)
5) Press the black button.(The IDU No. increase every 1 second in the zoning )
6) Set the Master IDU(Press the red button during 1.5seconds stop twinkling)
ROTARY 01 ROTARY 02
CAUTION
• Waiting for 80seconds after power on.
• The zoning information and Master IDU information remove from EEPROM after Auto-addressing.
• If there is installed the central control, it is impossible setting of Master IDU in zoning.
Configuración del número de grupo
Configuración del número de grupo de unidades interiores
① Compruebe que la alimentación de todo el sistema (unidad interior, unidad exterior) está desconectada. Si
no es así, desconéctela.
② Las líneas de transmisión conectadas a la terminal de INTERNET deberían estar conectadas al control
central de la Unidad exterior con la polaridad adecuada (A → A, B → B)
③ Conecte todo el sistema.
④ Configura el número de grupo y de unidades interiores mediante un mando a distancia cableado.
⑤ Para controlar varias unidades interiores en un grupo, configure la ID del grupo de 0 a F para este
propósito.
90
Unidad exterior
7 segment
No. of Indoor unit.
No. of HR unit branch.
No. of HR unit.
Unidades exteriores
SODU B SODU A
B
A
IDU B
IDU A
INT B
B(D)
INT A
A(C)