Rectify Faults - Vega VEGAPULS WL S 61 Manual De Instrucciones

Ocultar thumbs Ver también para VEGAPULS WL S 61:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Code
Cause
Text mes-
sage
S601
Danger of ves-
sel overfilling
Overfilling
Maintenance
The following table shows the error codes and
text messages in the status message "Mainte-
nance" and provides information on causes as
well as corrective measures.
Code
Cause
Text mes-
sage
M500
The data could
not be restored
Error during
during the reset
the reset "de-
to delivery
livery status"
status
M501
Hardware error
EEPROM
Error in the
non-active li-
nearisation
table
M502
Hardware error
EEPROM
Error in the
diagnostics
memory
M503
The echo/noise
ratio is too small
Measu-
for reliable
rement
measurement
reliability too
low
M504
Hardware defect
Error at a
device inter-
face
M505
Level echo can
no longer be
No echo
detected
available
VEGAPULS WL S 61 • 4 ... 20 mA
8.4
Rectification
Reaction when malfunction occurs
The operator of the system is responsible for
Make sure
taking suitable measures to rectify faults.
that there is no
further filling
Procedure for fault rectification
Check level in
The first measures are:
the vessel
Further comprehensive diagnostics options
are available with a PC with PACTware and the
suitable DTM. In many cases, the reasons can
be determined in this way and faults rectified.
Rectification
Check the 4 ... 20 mA signal
Connect a multimeter in the suitable measuring
Repeat reset
range according to the wiring plan. The following
Load XML file
table describes possible errors in the current
with sensor data
signal and helps to eliminate them:
into the sensor
Send instrument
for repair
Send instrument
for repair
Check installa-
tion and process
conditions
Clean the
antenna
Change polari-
sation direction
Check connec-
tions
Send instrument
for repair
Clean the
antenna
Remove possi-
ble false echoes
Optimize sensor
position and
Reaction after fault rectification
orientation
Depending on the reason for the fault and the
measures taken, the steps described in chapter
"Setup" must be carried out again or must be
8 Diagnosis, asset management and service

Rectify faults

Evaluation of fault messages via the adjust-
ment device
Checking the output signal
Treatment of measurement errors
Error
Cause
4 ... 20 mA
Fluctu-
signal not
ations
stable
of the
measured
variable
4 ... 20 mA
Electrical
signal mis-
connec-
sing
tion faulty
Voltage
supply
missing
Operating
voltage
too low
or load
resistance
too high
Current sig-
Elect-
nal greater
ronics
than 22 mA
module in
or less than
the sensor
3.6 mA
defective
Rectification
Set damping approp-
riate to the instrument
via the display and
adjustment module or
PACTware/DTM
Check connection
according to chapter
"Connection steps" and
if necessary, correct
according to chapter
"Wiring plan"
Check cables for
breaks; repair if neces-
sary
Check, adapt if neces-
sary
Exchange the instru-
ment or send it in for
repair
33