ECOTRONIC tech
Functions common to all double-panel Systems managed by the ECOTRONIC tech regulator
The ECOTRONIC Tech manages all the functions of the single-panel systems in a simultaneous way on panel
A and/or Solar Panel B.
Faults
LCD display off
Make sure the Regulator is powered: using a digital multimeter, check the presence of voltage at terminals 24
and 25.
In case of no voltage, check the wiring.
In case of suffi cient voltage ( Range 195 – 253 Vac), check the fuse. The fuse is located inside the regulator: to
access it, follow steps 1 and 2 of the section on Regulator Installation.
LCD display on
Any operation error conditions are shown on the regulator LCD display.
Fault code
Card
F81
F82
F83
F84
F85
F87
Fault 81 - Solar Collector B PT1000 Sensor S4 faulty
Only with SYSTEM 4
The sensor fault, understood as a short circuit or open circuit, causes deactivation of Solar Circulating Pump B.
On eliminating the fault, the protection is immediately deactivated.
To signal this fault, the symbol S4 will be deactivated, whereas the Fault symbol, symbol S4 and the backlight
will start fl ashing.
Fault 82 - Hot Water Tank NTC Sensor S2 faulty
The sensor fault, understood as a short circuit or open circuit, causes deactivation of the Solar Circulating Pump.
On eliminating the fault, the protection is immediately deactivated.
To signal this fault, the symbol S2 will be deactivated, whereas the Fault symbol, symbol S2 and the backlight
will start fl ashing.
Fault 83 - Solar Collector PT1000 Sensor S3 faulty
The sensor fault, understood as a short circuit or open circuit, causes deactivation of Solar Circulating Pump A.
On eliminating the fault, the protection is immediately deactivated.
To signal this fault, the symbol S3 will be deactivated, whereas the Fault symbol, symbol S3 and the backlight
will start fl ashing.
Fault 84 - Solar Collector Return NTC Sensor S1 faulty
Only with SYSTEM 4
The sensor fault, understood as a short circuit or open circuit, does not cause deactivation of the Solar Circu-
lating Pump. The system must simply work as though the Basic System were set. On eliminating the fault, the
protection is immediately deactivated.
To signal this fault, the Fault symbol and the backlight will start fl ashing.
112
Description
Fault
Solar Collector B PT1000 Sensor S4
Hot Water Tank NTC Sensor S2
Solar Collector A PT1000 Sensor S3
Solar Collector Return NTC Sensor S1
Regulator confi guration fault
Regulator confi guration fault
Cod. 3540V010 - 07/2010 (Rev. 00)