5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for follow ers (L2, L3). These settings are imposed on the w hole system by the
leader L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
Float
ds8-ds7
v oltage
oltage
14.1
13.8
of f
off
28.2
27.6
56.4
55.2
14.4
13.8
of f
on
28.8
27.6
57.6
55.2
14.7
13.8
on
of f
29.4
27.6
58.8
55.2
15.0
13.8
on
on
30.0
27.6
60.0
55.2
ds6: absorption time 8 or 4 hours (not relevant for L2, L3)
ds5: adaptive charging characteristic (not relevant for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (not relevant for L2, L3)
(the w ide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exem plary settings for stand-alone m ode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP sw itches of a new product are set to
'off' and do not reflect the actual settings in the microprocessor).
DS-8 Ch. v oltage
of f
DS-7 Ch. v oltage
on
DS-6 Absorpt. time
on
DS-5 Adaptiv e ch.
on
DS-4 Dy n. Curr. limit
of f
DS-3 UPS f unction:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptiv e charging: on
4 Dy namic current limit: of f
3 UPS f unction: on
2 Voltage: 230V
1 Frequency : 50Hz
To store the settings after the required values have been set: press the 'Dow n' button for 2 seconds (lower button to the right of
the DIP sw itches). The temperature and low-battery LEDs w ill flash to indicate acceptance of the settings.
The DIP sw itches can be left in the selected positions, so that the 'other settings' can alw ays be recovered.
Storage
Suitable f or
v oltage
13.2
Gel Victron Long Lif e (OPzV)
26.4
Gel Exide A600 (OPzV)
52.8
Gel MK battery
Gel Victron Deep Discharge
13.2
Gel Exide A200
26.4
AGM Victron Deep Discharge
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.2
Tubular plate (OPzS) batteries in
26.4
semi-f loat mode
52.8
AGM spiral cell
13.2
Tubular plate (OPzS) batteries in
26.4
cy clic mode
52.8
DS-8
of f
DS-8
DS-7
of f
DS-7
DS-6
on
DS-6
DS-5
on
DS-5
DS-4
of f
DS-4
DS-3
of f
DS-3
DS-2
on
DS-2
DS-1
on
DS-1
Step 2
Step 2
Example 2:
Example 3:
8, 7 OPzV 14,1V
8, 7 AGM 14,7V
6 Absorption time: 8 h
6 Absorption time: 8 h
5 Adaptiv e charging: on
5 Adaptiv e charging: on
4 Dy n. current limit: of f
4 Dy n. current limit: on
3 UPS f unction: of f
3 UPS f unction: of f
2 Voltage: 230V
2 Voltage: 240V
1 Frequency : 50Hz
1 Frequency : 50Hz
on = 8 hours
off = 4 hours
on = active
off = inactive (fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 230V
off = 240V
on = 50Hz
off = 60Hz
on
DS-8
on
of f
DS-7
on
on
DS-6
of f
on
DS-5
of f
on
DS-4
of f
of f
DS-3
on
of f
DS-2
of f
on
DS-1
of f
Step 2
Example 4:
8, 7 Tubular-plate 15V
6 Absorption time: 4 h
5 Fixed absorption time
4 Dy n. current limit: of f
3 UPS f unction: on
2 Voltage: 240V
1 Frequency : 60Hz