Parallel operation (see appendix C)
Step 1: Setting ds2 and ds1 for parallel operation of two or three units
Master
DS-8 AC-in-1
Set
DS-7 AC-in-1
Set
DS-6 AC-in-1
Set
DS-5 AC-in-2
Set
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
of f
DS-1 Master
on
The current settings (AC current limitation and charging current) are multiplied by the number of devices. How ever, the AC
current limitation setting w hen using a remote panel w ill alw ays correspond to the value indicated on the panel and should not
be multiplied by the number of devices.
Exam ple: 9kVA parallel system
- If an AC-in-1 current limitation of 20A is set on the master and the system consists of three devices, then the effective system
current limitation for AC-in-1 is equal to 3 x 20 = 60A (maximum input pow er 3 x20 x 230 = 13,8kVA).
- If a 30A panel is connected to the master, the system current limitation for AC-in-2 is adjustable to a maximum of 30A,
regardless of the number of devices.
- If the charging current on the master is set to 100% (70A for a Quattro 24/3000/70) and the system consists of three devices,
then the effective system charging current is equal to 3 x 70 = 210A.
The settings according to this example (9kVA parallel system) are as follow s:
Master
DS-8 AC-in-1 (3 x 20 = 60A)
DS-7 AC-in-1 (3 x 20 = 60A)
DS-6 AC-in-1 (3 x 20 = 60A)
DS-5 AC-in-2 na (30A panel)
DS-4 Charging current 3x70A
DS-3 Charging current 3x70A
DS-2 Master
DS-1 Master
To store the settings after the required values have been set: press the 'Up' button of the m aster for 2 seconds (upper button
to the right of the DIP sw itches, see appendix A, position K). The overload and low-battery LEDs w ill flash to indicate
acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP sw itches can now be used to apply the remaining settings (step 2).
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slav e 1
DS-1 Slav e 1
on
DS-8 na
of f
DS-7 na
of f
DS-6 na
DS-5 na
on
DS-4 na
on
DS-3 na
of f
DS-2 Slav e 1
on
DS-1 Slav e 1
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
of f
DS-2 Slav e 2
of f
DS-1 Slav e 2
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
of f
DS-2 Slav e 2
of f
DS-1 Slav e 2
Slave 2 (optional)
of f
on
Slave 2
of f
on
19