Gain calibration for sensor input (-5.0%...+5.0%):
P-06
These parameters act to adjust eventual mistakes caused by damages or
errors on thermocouple wiring and to set the precision of thermocouple
on a well definite point of the scale. If a pyrometric cone for kilns melts
at 1000°C but controller shows 990°C, it is enough to enter 1.0 on P-06 to
correct visualization.
7
Proportional band (0-1800 °C or °F)
P-07
8
Integral time (0/9999 sec). ( Zero excludes integral)
P-08
9
Derivative time (0.0/999.9 sec). (Zero excludes derivative)
P-09
10
Cycle time for output with proportional time (1/120 sec):
P- 10
These parameters set the values for P.I.D. control mode. In case of ON/
OFF modulation (proportional band set to 0), parameter P-10 acts as
hysteresis.
11
Measure units:
P- 1 1
Units of temperature measurement
0
°C
1
°F
12
Delayed start:
P- 12
Programming of delayed start (entering step 0) and Autotuning function
0
Step 0 enabled
1
Step 0 disabled
2
Step 0 enabled
3
Step 0 disabled
13
Treshold for alarm (0/3200 °C or °F):
P- 13
This parameter defines the treshold for alarm intervention.
14
Change of setpoint value during a firing curve:
P- 14
This parameter allows the setpoint values to be modified during a firing.
0
Setpoint change disabled
1
Setpoint change enabled
Auto-tune disabled
Auto-tune enabled
Auto-tune enabled
Auto-tune disabled
User manual ATR 900/901
-