INSTRUCTIONS AND WARNINGS FOR ADJUSTMENTS

Important
Before making any type of adjustment, acti-
vate all the safety devices provided and de-
cide whether staff at work and those in the
vicinity should be informed. In particular,
turn off the gas supply tap and prevent ac-
cess to all devices which might cause
unexpected health and safety hazards if
turned on.

ADJUSTING GAS CONTROL VALVE MINIMUM SETTING

Important
This adjustment is only required if the
type of gas to be connected is different
from that used for testing after the conver-
sion procedure has been carried out (see
page 15). Before making this adjustment,
check that the gas supply pressure is the
same as the rated pressure for the type of
IT
gas in use (see table at back of manual).
To carry out this operation, proceed as follows.
GB
1 - Turn off the gas supply tap.
DE
FR
ES
English

ADJUSTMENTS

B
A
- 16 -
Important
Adjustments must be carried out by autho-
rised, qualifi ed staff , in accordance with
the relevant legal requirements.
2 - Pull off the knob (A).
3 - Undo the screws (C) and remove the control
panel (B).
4 - Remove the injector (D) and replace it with the
one suitable for the type of gas in use (see table
at back of manual).
5 - After making the setting, seal the screw with
paint.
6 - Replace the control panel (B) and the knobs (A)
on completion of the operation.