LERBAKKEN 10, 8410 RØNDE DENMARK.
Installation notes
The sensor circuit is not infallibly galvanic isolated from the supply output circuit. However, the
galvanic isolation between the circuits is capable of withstanding a test voltage of 500Vac
during 1 minute.
For installalation in dust the following instructions apply:
The transmitter shall be mounted in a metal enclosure that is providing a degree of protection
of at least IP6X according to IEC 60529.The surface temperature of the enclosure is equal to
the ambient temperature +20 K, for a dust layer with a maximum thickness of 5 mm.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed
Revision date:
2011-02-01
22
WWW.PRELECTRONICS.COM
Version Revision
V3R0
6
335V1 1 0- ES
6335QI01
0Page:
2/2