Installation notes
The sensor circuit is not infallibly galvanic isolated from the supply output circuit. However, the
galvanic isolation between the circuits is capable of withstanding a test voltage of 500Vac
during 1 minute.
For installalation in dust the following instructions apply:
The transmitter shall be mounted in a metal enclosure that is providing a degree of protection
of at least IP6X according to IEC 60529.The surface temperature of the enclosure is equal to
the ambient temperature +20 K, for a dust layer with a maximum thickness of 5 mm.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed
Revision date:
2011-02-01