4. INSTALLATION ADVICE
The electrician is responsible for selecting a cable thickness & safety components appropriate
for the specific situation and according to regulations;
Wiring advice*
Power cable size
Earthing advice*
Required nominal
input voltage @
charge point
MCB
RCD
Ethernet connection
cable requirements
*
The electrician is always responsible for selecting a cable thickness appropriate for the specific
situation and according to regulations;
** 3-phase charge point can also be connected to 1-phase. In this case the charge point can only
charge on 1-phase;
*** The electrician must select a suitable MCB to match the amperage setting of the charge point,
taking into account MCB manufacturer specifications;
NOTE: The charge point can be set between 10 A and 16 A / 32 A (depending on version);
INSTRUCTION MANUAL – P13
- Wire for the maximum hardware amperage under continuous load;
- Calculate with a COS-Phi of 0.8;
- Calculate with a max allowable voltage drop over the cable of 2%;
- Use shielded cable for underground wiring;
Cable grommets sizes
Maximum cable terminal block
TN-system
TT-system
Single phase**
Triple phase**
C-characteristic***
30mA Type B, or 30mA Type A in combination with appropriate equipment that
guarantees power shutdown at DC leakage of more than 6mA.
Standard CAT5 or CAT6 Ethernet cable (UTP cable with RJ45 connectors)
Ø 10mm - Ø 22,5mm
10mm2 solid wire
6mm2 stranded wire with end ferrules
PE-cable
Separately installed grounding
electrode < 100 Ohm spreading
resistance
230V +/-10% 50Hz
400V (3 x 230V+N) +/-10% 50Hz
0506NM20INT02