ENGLISH
-0: three probes without control of the cooling fans.
-1: four probes with control of the cooling fans.
-2: four probes without control of the cooling fans.
-3: three probes with control of the cooling fans.
-4: advanced programming menu.
Default configurations: P=140,A=160,L=90,H=100,F=0.
Modify it pressing buttons UP/DOWN and confirm by <ENTER>.
In case of choice F=4 jump to menu: ADVANCED MENU PROGRAMMING,
in other case continue here.
On the display appears the letter "P" (Pre-alarm) and the set
temperature from the last programming.
The pre-alarm temperature is set through UP/DOWN buttons.
After setting the pre-alarm temperature push <ENTER>.
The letter "A" (Alarm) appears together with the set temperature of the
last programming. If the new pre-alarm temperature is higher than old
alarm,the device propose a new pre-alarm temperature more 1 degree.
Modify it pressing buttons UP/DOWN and confirm by <ENTER>.
In case of choice F=0 or F=2 the programming procedure is finished, in
other case continue here.
Now on the display appears the letter "L". for the choice of the lowest
temperature under which the fan switches off.
Modify it pressing buttons UP/DOWN and confirm by <ENTER>.
The letter "H" appears to choose the maximum temperature over which
the fan switches on.
Modify it pressing buttons UP/DOWN and confirm by <ENTER>.
Soon out of programming procedure the device executes a LAMP/TEST.
System is prearranged in automatic way and visualises so the maximum
measured temperature and the relative channel.
Anyway the necessary time for programming is checked. Over 1 minute
from beginning of the programming phase, the same is interrupted and is
not saved so the previous set limits remain active.
The visualisation mode can be modified from manual to automatic system
pressing the special button AUTO/MANUAL.
During automatic working
the higher temperature and the relative
number of channels appear on the display.
In this mode is possible to read all the parameters of the device.
Pushing buttons UP/DOWN is possible to show in order:
Current value of active channels, configuration (parameter F), letter "P"
(pre-alarm), letter "A" (alarm), fan threshold "L" and "H" if active.
11