The unit is completely wired in the
factory and to start it up it is neces-
sary to have a power supply that works
according to the indications on the
rating plate of the unit, with cut off with
protective devices on the line.
The cable cross sections and the scaling
of the line main switch are purely indi-
cative.
It will be up to the installation engineer
to properly dimension the power line
depending on the length, type of cable,
unit consumption and physical position.
ANZ (°) - ANZ A
(230V single phase)
0207
0257
SECT. A
mm
2
4
4
SECT. B
mm
2
0,5
0,5
Terra
mm
2
4
4
IL
A
16
20
ANZ (°) - ANZ A
(400V three phase)
0207
0257
SECT. A
mm
2
1,5
1,5
SECT. B
mm
2
0,5
0,5
Terra
mm
2
1,5
1,5
IL
A
8
10
ANZ K - ANZ J
(230V single phase)
0207
0257
SECT. A
mm
2
10
10
SECT. B
mm
2
1
1
Terra
mm
2
10
10
IL
A
32
32
ANZ K - ANZ J
(400V three phase)
0207
0257
SECT. A
mm
2
4
4
SECT. B
mm
2
1
1
Terra
mm
2
4
4
IL
A
16
16
10
Electrical wiring
All the electrical wirings must comply
with the regulations in force at the time
of the installation.
The diagrams and schematics in this
documentation must only be used as
an aid for the setting up of the electrical
lines. Refer to the wiring diagram sup-
plied with the device, for installation
requirements.
N.B.
Check that all power cables are cor-
0307
0417
6
6
0,5
0,5
6
6
25
25
0307
0417
0507
0807
2,5
4
4
6
0,5
0,5
0,5
0,5
2,5
4
4
6
10
13
13
16
0307
0417
10
10
1
1
10
10
45
45
0307
0417
0507
0807
6
6
6
10
1
1
1
1
6
6
6
10
20
20
20
32
rectly secured to the terminals when
switched on for the first time and after
30 days of use. Afterwards, check the
connection of the power cables every
six months. Slack terminals could cause
the cables and components to ove-
rheat.
Cross sections recommended for the
maximum length of 50 m. The cross
section of the cable and the dimension
of the line main switch are purely indi-
cative.
0907
1007
1507
2007
6
10
16
16
0,5
0,5
0,5
0,5
6
10
16
16
25
32
40
50
0907
1007
1507
2007
10
16
25
32
1
1
1
1
10
16
16
16
40
50
63
80