**** The outputs OUT14 and OUT15 can only be used as 2nd controller output for channel 1 or channel 2 if this slot is not already used
as power supply output for the standard signal input 2 at channel 2.
4.3.2
Versatronic cooling water
Design C1, see
Measuring
channel
Cooling tower 1 IN 7 *
Drainage 2
(additional
measurement 1)
Drainage 3
(additional
measurement 2)
All drainages
Design C2, see
Measuring
channel
Cooling tower 1 IN 7 *
Cooling tower 2 IN 8 *
Drainage 3
(additional
measurement 1)
Drainage 4
(additional
measurement 2)
Ä Chapter 5.2 'Material code' on page 16
Inputs and outputs
IN 4
IN 1
OUT 3
OUT 2
OUT 12 *
OUT 13 *
OUT 4
IN 8 *
IN 5
IN 2
OUT 14 *
OUT 5
IN 9 *
IN 11 *
IN 3
OUT 15 *
OUT 16 *
OUT 1
Ä Chapter 5.2 'Material code' on page 16
Inputs and outputs
IN 4
IN 1
OUT 3
OUT 2
OUT 12 *
OUT 4
IN 5
IN 2
OUT 13 *
OUT 14 *
OUT 15 *
OUT 5
IN 9 *
IN 11 *
IN 3
OUT 16 *
OUT 18
IN 10 *
IN 11 *
IN 13 *
Explanation
Cooling tower 1 input measurement signal
Cooling tower 1 input temperature
Cooling tower 1 release input
Cooling tower 1 output desalination
Cooling tower 1 output Dos. Biocide 1
Cooling tower 1 output Dos. Biocide 2
Cooling tower 1 output circulation pump
Cooling tower 1 standard signal output
Drainage 2 input measurement signal
Drainage 2 input temperature
Drainage 2 release input
Drainage 2 controller output 1
Drainage 2 standard signal output
Drainage 3 input measurement signal
Drainage 3 input temperature
Drainage 3 release input
Drainage 3 controller output 1
Drainage 3 standard signal output
Common alarm output for all drainages
Explanation
Cooling tower 1 input measurement signal
Cooling tower 1 input temperature
Cooling tower 1 release input
Cooling tower 1 output desalination
Cooling tower 1 output Dos. Biocide
Cooling tower 1 output circulation pump
Cooling tower 1 standard signal output
Cooling tower 2 input measurement signal
Cooling tower 2 input temperature
Cooling tower 2 release input
Cooling tower 2 output desalination
Cooling tower 2 output Dos. Biocide
Cooling tower 2 output circulation pump
Cooling tower 2 standard signal output
Drainage 3 input measurement signal
Drainage 3 input temperature
Drainage 3 release input
Drainage 3 controller output 1
Drainage 3 standard signal output
Drainage 4 input measurement signal
Drainage 4 input temperature
Drainage 4 release input
13
Unit Description
417102279 Rev. 2-08.2020
Tabla de contenido
loading

Este manual también es adecuado para:

255201

Tabla de contenido