Robuschi ROBOX evolution Manual De Uso página 64

Unidad de vigilancia electrónica
Tabla de contenido
0x0806
bitmask
2
0x0807
bitmask
2
0x0808
bitmask
2
0x0809
bitmask
2
0x080A
int
2
0x080B
int
2
0x080C
int
2
0x080D
int
2
0x080E
int
2
0x080F
int
2
0x0810
int
2
0x0811
bitmask
2
Record download
It's possible to download Sentinel record by MODBUS interface.
There is no specific function to download file. The function 0x03 used in the preceeding paragraphs to read data is used in this procedure too.
Reading procedure is the following:
- Read Block 10 in order to position at the beginning of the recorded data and download the first 8 record.
- Read Block 11 to move forward on next 8 records and read them.
- Repeat the previous step until there are records to download.
Whenever reading procedure of Block 11 will fail and it is required to repeat it in order to avoid to move forward by 8 records loosing data
contained in the previous reading is to be used Block 12 which allow to read the 8 current records without moving forward in the records list.
Referring to these latest three blocks (10,11 and 12), the acquisition will require always the complete lenght of 144 bytes (8 records). In case
a minor amount of data would be present the reply will contain the available ones and the third byte of the reply, containing the byte number of
the data, will be consequently set. Sequential reading, exceedind end of data will return always zero lenght.
Block 10: Record, start reading
Addr
Type
Size Name
0x0A00
Record[8]
144
Block 11: Record, pointer moving and reading
Addr
Type
Size Name
0x0B00
Record[8] 144
Block 12: Record, read again current record
Addr
Type
Size Name
0x0C00
Record[8] 144
64
W3-0A5 12-I
ALWARN
Active visual alarms, visual alarm AL-W-<i> is active if bit b
b0
AL-W-01
b1
AL-W-02
b2
AL-W-03
b3
AL-W-04
b4
AL-W-05
b5
AL-W-06
b6
AL-W-07
b7
AL-W-08
b8
AL-W-09
b9
AL-W-10
b10
AL-W-11
b11
AL-W-12
ALMAINT
Active maintenance alarms, maintenance alarm AL.M<i> is active if bit b
is:
b0
AL.M1
b1
AL.M2
b2
AL.M3
b3
AL.M4
b4
AL.M5
b5
AL.M6
DIGIN
Digital input status, bit = 1 indicate that input is closed, bit association is:
b3 = transistor for oil level drive side
b4 = transistor for oil level rear side
b6 = Presenza espansione
b7 = Test
OPTIN
Opto input status, bit = 1 indicate that input is closed, bit association is:
b0 = emergency button
b1 = Motor current protection
b2 = Motor PTC
b3 = Fan motor current protection
b5 = rpm direction sensor
b6 = rpm sensor
b7 = IN4 main motor Start/Stop
P1
Pressure P1 instantaneous measure [mbar]
P2
Pressure P2 instantaneous measure [bar*10]
P3
Pressure P3 instantaneous measure [bar*10]
T2
Temperature T2 instantaneous measure [°C*10]
T3
Temperature T3 instantaneous measure [°C*10]
T4
Temperature T4 instantaneous measure [°C*10]
SPEED
Compressor speed [rpm]
RELE
relè status, bit = 1 indicate relè ON, bit association is:
b0 = Ventilation Fan
b1 = Alarm
Notes
RECORDS
Read the first 8 records in EEPROM (oldest ones).
Notes
RECORDS
Move forward the read internal EEPROM pointer by 8 record and read the 8 current
record.
Notes
RECORDS
Read the first 8 records without moving forward the read internal EEPROM pointer.
is 1, bit association is the following:
<i-1>
Set data lost
RS232 communication fault
RS485 communication fault
Pre. Al. Rpm max.
Pre. Al. P1
Pre. Al. P2
Pre Al. T2
Pre Al. T3
Pre Al. T4
Clock fault
rpm sensor falut/ brocken belt
Wrong rotation with machine not running
Count-down 6-M1- expired
Count-down 6-M2- expired
Count-down 6-M3- expired
Count-down 6-M4- expired
Count-down 6-M5- expired
Count-down 6-M6- expired
is 1, bit association
<i-1>