THIS CAN BE DONE IN EITHER OF TWO WAYS
MODE 3 - WITH ENCODER ONLY (DIP 7 ON AND JUMPER S3
OPEN)
- WITH ENCODER AND ELECTRIC LIMIT SWITCHES (IF
APPLIED) (DIP 7 ON AND JUMPER S3 CLOSED)
- WITHOUT ENCODER BUT WITH ELECTRIC LIMIT
SWITCHES (IF APPLIED) (DIP 7 OFF AND JUMPER S3
CLOSED)
MODE 4 - TIMED (DIP 7 OFF AND JUMPER S3 OPEN)
MODE 3
1 - Start with the gate completely closed and with mechanical stopper
already regulated like fig.10.
2 - Put DIP 2 in the ON mode => LED DL9 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, the
ENCODER stops M1 (with storage of the encoder readings and the
time) and the delay countdown priot to automatic closing starts (max
5 minutes).
5 - Press PROG. => delay countdown prior to automatic closing stops
and M2 closes. At the same time LED DL9 stops blinking to signal exit
from the programming mode. At this point, the safety devices and
other gate controls will resume normal operation (inversions, stops,
alarms, etc.).
6 - The gate will stop at the end of the ENCODER countdown.
7 - AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
NOTE: The same procedure applies to electric limit switches (S3 closed).
With S3 closed, gate travel is determined by the electric limit
switches and not by the encoder, which only acts as a safety
device.
MODE 4
1 - Start with the gate completely closed.
2 - Put DIP 2 in the ON mode => LED DL9 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, wait one
second then press PROG. => M1 stops and the delay countdown
prior to automatic closing starts (max 5 minutes).
5 - Press PROG. => delay countdown prior to automatic closing stops
and M1 closes. At the same time LED DL9 stops blinking to signal exit
from the programming mode. At this point, the safety devices and
other gate controls will resume normal operation (inversions, stops,
alarms, etc.).
6 - The gate will stop at the end of the ENCODER countdown.
7 - AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
O
PERATION OF THE OPERATING ACCESSORIES
OPENING BUTTON (with timer function)
When the gate is standstill, the button operates the opening mode. If you
push this button when the gate is on closure, It opens again.
TIMER FUNCTION
This function is useful In the rush hours, when vehicle traffic is slow (e.g.
entry/exit of workers, emergencies In residential or parking areas and,
temporary, for removals).
APPLICATIONS
By connecting a switch and/or a daily/weekly timer (in place or in parallel
with the opening button N.O. "COM-OPEN"), it is possible to open the
automation or to keep It open, as long as the switch is on or the timer is
activated.
When the automation is open, all operating functions are inhibited.
If the automatic closing Is started, by releasing the switch or at the time
set before, the automation immediately closes; if not, you need to operate
a command.
CLOSING BUTTON (COM-CLOSE)
When the gate Is standstill, It operates the closing.
JOGGING OPERATION BUTTON (COM-K BUTTON)
DIP5 - OFF => It cyclically commands open-stop-close-stop-open-etc.
DIP5 - ON => It opens the gate when this Is closed. If It Is operated while
the gate Is opening, It has no effect. If It Is operated when
the gate is open, it closes the gate and, If It Is operated
while the gate Is closing, It opens the gate again.
RADIO TRANSMITTER
DIP4 - OFF => It cyclically commands open-stop-close-stop-open-etc.
DIP4 - ON => It opens the gate when this is closed. If It Is operated while
the gate Is opening, It has no effect. If It Is operated when
the gate Is open, It closes. If It Is operated while the gate
Is closing, It opens the gate again.
AUTOMATIC CLOSING
Pause times before the automatic closing of the gate are set with the
timing procedure.
The maximum pause time is 5 minutes.
Pause time can be started or stopped by DIP3 (ON started).
ELECTRIC LOCK IN OPENING PHASE
Set DIP10 to ON to enable control of the electric lock in the opening
phase.
ELECTRIC LOCK AND RELEASE PULSE IN OPENING PHASE
Set DIP11 to ON to enable the release pulse of the electric lock in the
opening phase (provided S2 DIP10 is set to ON).
With the gate closed, pressing an opening command will cause the gate
to perform the closing movement for 0.5s (in this phase the Encoder(s)
is/are not enabled), and simultaneously the electric lock is activated
(followed by 0.5s pause and then by opening of the gate).
GATE LEAF RELEASE ASSIST:
With the electric lock release pulse active (DIP11 - ON), when the gate is
closed a direction reversal manoeuvre is performed for a fixed time of
0.2s to facilitate manual release (in this phase the Encoder is not
enabled).
OPERATION AFTER BLACK-OUT
When mains electrical power is restored press the opening button (K,
OPEN, radio).
The gate will open. Let the gate close itself with automatic closure or wait
that the flasher stops blink first to command the closing movement. This
operation is valid to obtain the leaves position readjustment. During this
phase all safety devices are active.
(#) SAFETY DEVICES ARE ACTIVE DURING THE PROGRAMMING
AND THEIR INTERVENTION STOPS IT (THE LED 9 BLINKS NO MORE
BUT REMAINS CONSTANTLY TURNED ON).
TO REPEAT THE PROGRAMMING, POSITION DIP1 AND 2 ON MODE
OFF, CLOSE THE GATE AND REPEAT THE PROCEDURE
DESCRIBED ABOVE.
S
AFETY ACCESSORIES OPERATION
SAFETY ENCODER
It serves as a safety device both during opening and on closure,
with movement reversion.
DIP 7 (ON) OPERATES THE MOTOR WITH ENCODER.
If the Encoder does not work (due to a failure In the power supply,
disconnected wires, broken or defective disk), the gate Is not operated.