4. Setting up unit - SET UP
4.3.4 Counter reset
48
Measurement point name or description of the function of this input. 10
Identifier
character.
Additional information to the digital channel (e.g. respective measurement
point number, tag identification system in power stations etc.). 13 characters.
Hints: Can only be set up if "With additional channel info" is selected up in
Additional information
"Basic settings - Channel identifier".
If required the additional info can be listed on screen together with the
channel identifier in normal operation (select the display mode using the
ïï push buttons).
"Can only be used as a control input": When active releases the allocated
control function in the unit.
"Starts plot": Plot/storage are only operational so long as the control input is
active.
Hint: The actual measured values continue to be displayed. Alarm set points
are no longer monitored.
Action
"Setting up block": Setting up of the unit using the push buttons is possible
when the input is active.
"Time synchronisation": A control impulse from an external contactor (e.g.
mater clock) synchronises the internal clock of the unit: If this is between 0
and 29 seconds the seconds are reset to 00 without an increase in minutes. If
the clock seconds are between 30 and 59 seconds then they are reset to 00
and the minutes are increased by 1 minute.
Copies all settings of the actual channel to the selected channel. Saves time,
when similar inputs are connected.
Copy settings
Hint: The measurement point identifier is also copied to the target channel.
The last characters are however substituted by the channel number (e.g. "02",
"03", ...).
Description of the condition when the control input is active. 5 character.
Description "H"
Logic High = +12...+30 V.
Description of the condition when the control input is not active. 5 character.
Description "L"
Logic Low = -3...+5 V.
Event text L - H
Description of condition change from Low (-3...+5 V) to High (+12...+30 V).
Event text H - L
Description of condition change from High (+12...+30 V) to Low (-3...+5 V).
"Display+acknowledge": Message must be acknowledged ("OK") by
operating a push button. This message consists of date, time and channel
Event text
identifier with alarm set point value (alternatively the event text L-H/H-L has a
text set up).
"Only record": Events are recorded and placed in the event list.
Daily or totalizer counters can be manually reset. Example: Reset after initial
Reset to zero
plant installation. The graphics or storage is not influenced (evidence!).
• (Option "Integration"): Setting only
necessary if the counters from
integrated analogue channels are to
be reset to zero.