S&P DOMO Instrucciones De Uso página 21

Control y gestión de recuperadores con microprocesador
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

You move around the menu with the up-down arrows and clicking on the one involved. For the description
of the various menus refer to the ADVANZ manual. Note that for the connection to the web server is
successful the first three fields of the ip address of the machine and the one of the computer connected
must match. For example if our ip address is 192.168.1.243 the one of the PC must be 192.168.1.xxx.
Addressing the electronic board
MODBUS-RTU:
The address of the electronic board is an eight digit binary number, so are available up to 256 addresses.
The address composition is made by the micro-switches of SW1 (see Figure 1), in accordance with the
following specification:
Bit-address_0: switch S1.1 (OFF= 0, ON =1)
Bit-address_1: switch S1.2 (OFF= 0, ON =1)
Bit-address_2: switch S1.3 (OFF= 0, ON =1)
Bit-address_3: switch S1.4 (OFF= 0, ON =1)
Bit-address_4: switch S1.5 (OFF= 0, ON =1)
Bit-address_5: switch S1.6 (OFF= 0, ON =1)
Bit-address_6: switch S1.7 (OFF= 0, ON =1)
Bit-address_7: switch S1.8 (OFF= 0, ON =1)
MODBUS TCP-IP :
To use Modbus Tcp-ip with a program different from web server all dip switches must be set to 1.
If you want to change the IP address this is possible in two different ways :
SOFTWARE:
Open web server ,navigate to menu "installer" (pass 5678) ,under the voice "ip address" enter the desired
ip ,save and then power cycle the machine. Clearly that if you still want to interact with the web server you
will have to upgrade the ip address in the bar of your browser.