Recommendation:
Cables should follow the direction
indicated by the arrows on the enclo-
sure.
The use of 500 mA gG fuses is
recommended for voltage input pro-
tection when using specific cable for
voltage.
SOCOMEC - Réf. : 875 452A
SCREW-IN CONNECTION
Remove the two covers to access the
terminals.
Tighten terminal screws
to trap cable
VN
IN
V1
IN
• Single-phase (1 BL):
- Current measurement:
Connect top and bottom of I1.
- Voltage measurement:
Connect terminals V1 and VN.
NB: It is imperative to use cable with
a maximum section of 2.5mm
ween terminals V2 and VN.
• Two-phase (2BL):
- Current measurement:
Connect top and bottom of I1
and I2.
- Voltage measurement:
Connect terminals V1 and V2.
For optimal operation use cable
connections with the following
sections:
PULSE OUTPUT
A reed relay (100 V - 0,5 A - 10 VA)
available on the Countis ATd provides
a pulse for active energy, the value
being fixed at 100 Wh. The duration
can be programmed (see § program-
ming).
POWER
I1
V2
I2
V3
I3
I1
I2
I3
1
2
100 Wh
100 Wh
• Three-phase (balanced) with or
without neutral (3 or 4 BL):
- Current measurement:
Connect top and bottom of I1.
- Voltage measurement:
Connect V1, V2, V3 and VN (if
neutral is distributed).
2
bet-
• Three-phase (unbalanced) with
or without neutral (3 or 4 NBL):
- Current measurement:
Connect top and bottom of I1, I2,
I3 and IN (if neutral is distributed).
- Voltage measurement:
Connect V1, V2, V3 and VN
(if neutral is distributed).
4mm
2
(flexible and rigid) from 0 to 32A,
10mm
2
(flexible and rigid) from 32 to 63A,
16mm
2
(flexible and rigid) from 63 to 80A.
VN
IN
V1
IN
Tighten
terminal screws
to trap cable
POWER
I1
V2
I2
V3
I3
I1
I2
I3
1
2
100 Wh
100 Wh