BA_REFUsol 008K-023K_V04.0_WW
4 Commissioning
Before commissioning the REFUsol
Confirm the correct power supply connection
Confirm the correct connection of PV strings
Confirm that connectors are protected such that they cannot be pulled off inadvertently
In the event of installation in France, the device must be provided with the warning sticker laid
down by UTE C 15-712-1. The warning sticker is included in the delivery.
VORSICHT
CAUTION
4.1 Switching on the Device
1
Verify that the device is connected to line voltage. If not, insert the external power fuse or
turn on the circuit breaker.
2
Set the DC isolating switch on the inverter to the ON position.
inverter will not start running with connected PV field before the DC isolator is switched on.
Note:
4.2 Setting the Country Code and the Menu Language
The country code defines the country-specific network monitoring parameters. The menu
language is automatically set when the country code is selected. Thereafter, the menu language
can be selected as desired at any time, independent of the country code set in the menu.
30
®
, be sure the following steps have been completed:
Risk of electric shock!
●
Before switching on the device, check whether the connectors are
securely fitted (locked).
●
Do not pull off the connectors of the PV generator before you have met
the following requirements:
- Set the DC isolator on the inverter to "OFF".
- Check whether the DC cables of the PV generator are de-energized.
- Enable the power supply line and protect the voltage supply against
- being reactivated.
Risk of electric shock and fire caused by high leakage current!
-
Before connecting the device to the supply circuit, establish a
-
ground connection.
The control panel is only active with activated DC voltage.
The control panel, including its staus indicators, display and operator keys, is
only active with activated DC voltage because the electronics of the inverters
is exclusively supplied from the DC side.
The
Copyright REFUsol GmbH