2 Installation
2.1 Assembly Site Requirements
The inverter is provided with convection cooling and is therefore designed for attachment to a vertical
wall. The device is attached by means of a self-centering wall-mounting plate.
Note:
The assembly site must be shaded.
The device may only be mounted in a vertical position.
For the assembly is to choose a solid wall or metal structure that corresponds to the fire
protection class F30 and the load capacity of 40kg per unit. Relevant assembly regulations
are to be adhered.
Mount the device at an appropriate distance from combustible materials.
We recommend that you mount the device at eye level to ensure optimum user comfort.
Owing to its protection type (IP65), the device can also be mounted in outside areas.
Note:
To allow for the heat dissipation required, keep the following minimum distances from the
ceiling and wall as well as from neighbouring devices.
Minimum
distances
CAUTION
24
To prevent accidents when installing and servicing, free and safe access to
the devices must be ensured.
Do not cover the cooling ribs of the heat sink. Failure to observe this
specification could void your warranty.
At the sides
50 mm or
1.9685 inches
Inverters should in no case be mounted on top of each other without a
Power Cap otherwise the convection cooling will be affected!
At the
500 mm or
top
19.685 inches
At the
500 mm or
bottom
19.685 inches