Danfoss FCM 300 Serie Guía Rápida página 8

Ocultar thumbs Ver también para FCM 300 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
NB!:
Do not lift or remove the entire plastic cover.
The voltage on the FC motor is dangerous
and may lead to material damage, serious
injury or it may be fatal.
NB!:
Mains terminals L
, L
1
Make sure that your mains supply corresponds
to the voltage required by the FC motor (see
inverter label), TT and NT mains .
Connect the three mains phases to terminals L
L
and the earth to the separate terminal provided.
3
Tightening Torques
L
, L
, L
FCM 305-340
1
2
3
L
, L
, L
FCM 355-375
1
2
3
Earth ground
FCM 305-375
Fixed wires:
Rated temperature for fixed wires min. 60° C or 140° F.
Use copper conduction only.
NB!:
You cannot change the rotation direction of the
motor by shifting around the phases. The direct-
ion of rotation is clockwise by default. Another
direction of rotation can be programmed, see the Design
Guide.
Prefuses Max.
UL
1)
FCM 305-322
FCM 330-340
FCM 355-375
IEC
1)
FCM 305-375
1)
Type gG prefuses must be used. If you want to maintain
UL/cUL you must use prefuses of the type Bussmann KTS-R
500 V or Ferraz Shawmut, type ATMR (max. 30A). The fuses
must be placed for protection in a circuit that is capable of
supplying a maximum of 100,000 amps RMS (symmetrical),
500 V maximum.
Control terminals
For information on terminal blocks X100, X101 and
X102, please see table A, B and C.
X100: Terminal block for data communication
Terminal
Function
No.
1
P RS 485
2
N RS 485
3
5 V DC
4
0 V DC
Table A
MG.03.A3.62 – VLT is a registered Danfoss trademark
VLT
®
DriveMotor FCM 300 Quick Setup
and L
:
2
3
, L
and
1
2
0,5-0,6 Nm
1,2-1,5 Nm
3,4 Nm
10A
15A
25A
25A
for connection to
bus or PC
Supply for RS 485 bus
X101: Terminal block for analog/digital control signals
Terminal Function
Example
No.
1
Analog input (0-20 mA)
signal
2
Analog (0-10 V)/
digital input 2
3
Digital input (or pulse) 3
4
Digital input
(or precise stop) 4
5
Digital input (other) 5
(fixed speed)
6
24 V DC supply for digital
inputs (max 50 mA)
7
10 V DC supply
for potentiometer
(max. 15 mA)
8
0 V for terminals 1-7 and 9
9
Analog (0-20 mA)
digital output
Table B
X102: Terminal block for relay output
Terminal
Function
No.
1-2
Make (normally open)
1-3
Brake (normally closed)
Table C
RS 485 switch
For terminating an RS 485 interface serial
communication, the bus must be terminated by a
resistor network at both ends. This is provided by setting
both switches to ON.
LEDs
The FC motor has five LEDs which indicate the status of
the FC motor:
LED 300 (red):
Fault trip
LED 301 (yellow):
Warning
LED 302 (green):
Power on
LED 303-304 (green): Communication
EMC-correct installation
The control cables must be screened cables to ensure
EMC-correct electrical installation.
Connect the screen to earth at both ends.
Avoid installation with twisted screen ends (pigtails),
since this ruins the screening effect at high frequencies.
Use cable clamps instead.
Feedback-
Hastigheds-
reference
Reset
Start
Jog
Fault indication
7