Configuring The Maximum Battery Charge Power From The Auxiliary Grid/Genset; Configuring The Back-Up Function; Configuring The Ac Voltage And Rated Frequency Of The Loads In Stand-Alone Installations - Ingeteam INGECON SUN STORAGE 1Play Manual De Instalacion Y Uso

Ocultar thumbs Ver también para INGECON SUN STORAGE 1Play:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Display control
Setting
Reboot state of
charge of supply to
the consumers using
SOCRECX
photovoltaic energy
(no diesel generator
available) (%).
Minimum state
of charge to fully
SOCDESCX
discharge the batteries,
stopping the supply to
the consumers (%).
18.9. Configuring the maximum battery charge power from the
auxiliary grid/genset
This option allows to set the maximum power for charging the batteries from the auxiliary grid or generator.
To configure this parameter, open MAIN MENU > CONFIGURATION > OPERATION MODE > MODE > open the
selected mode> CHARGING POWER and specify the maximum power in watts.
When the inverter is connected to the grid or generator, the batteries are charged from said AC source when the
state of charge (SOC) is lower than the set SOC MIN (see "18.8. Configuring the operation mode and its settings").

18.10. Configuring the back-up function

By default these inverters are configured with the back-up function activated. Therefore, in the event of a
distribution grid failure, the inverters internally disconnect the installation from the distribution grid and provide
the necessary power to the consumers from the batteries and the PV array. To do this, the consumers must be
connected to the inverter in the LOADS input (see "9. Connecting the consumption grid").
The response time of the system in the event of a grid outage is imperceptible for most of the consumers (12 ms).
The back-up function must be used in countries that allow this operation mode, taking into account the TT or TN
grounding system used by the grid operator.
Only in TT grounding systems is it necessary to install an external Normally Open contactor to reference the neutral
from the consumption grid to ground in the event of a grid outage.
INFO
For more information about this type of installation, see the "Technical guide for installations with
INGECON SUN STORAGE 1Play" available on the Ingeteam website.
To configure the back-up function, open MAIN MENU > CONFIGURATION > OPERATION MODE > BACK-UP
FUNCTION.
18.11. Configuring the AC voltage and rated frequency of the loads
in stand-alone installations
In stand-alone installations these units allow to power the consumption grid with configurable AC voltage and
frequency.
To configure the AC voltage and rated frequency, open the MAIN MENU > CONFIGURATION > INVERTER.
Setting
RMS VOLTAGE
FREQUENCY
ABH2013IQM01_C - Installation and Operation Manual
Stand-Alone
UPS (back-up)
Reboot state of charge
of supply to the critical
consumers using
photovoltaic energy (no
grid available) (%).
Minimum state of
charge for discharging
batteries to the critical
consumers when the
distribution grid is not
available (%).
Rated voltage supplying the AC consumers (V).
Rated frequency of the consumer output (Hz).
Operation mode
Self consumption
Reboot state of charge of
supply to the consumers
using photovoltaic
energy when the grid
is not available and the
back-up function is
activated (%).
Minimum state of charge
for discharging batteries
to the consumers when
the distribution grid is
not available and the
back-up function is
activated (%).
Description
Ingeteam
EN
Grid support
ES
Informative value, not
used. The back-up
FR
must be deactivated.
PT
Informative value, not
used. The back-up
must be deactivated.
65