Action: Sets all state variables to the default values
Response from UPS: $FACTORY SETTINGS RESTORED<CR>
SEND QUERIES IDENTIFY
Request that the unit identify itself.
Send Query to UPS: ?ID<CR>
Action: Model number and firmware revision will be provided
Response: $FURMAN<CR>
$F1500-UPS<CR>
$FIRMWARE revision<CR>
OUTLET STATUS
Requests the on/off status of the outlet banks.
Send Query to UPS: ?OUTLETSTAT<CR>
status = {ON, OFF}
Action: On/off status for outlets will be provided
Response: $BANK1 = status<CR>
$BANK2 = status<CR>
$BANK3 = status<CR>
$BANK4 = status<CR>
POWER STATUS
Requests the status of the input voltage. The responses are the same as Power Fault Status Change.
Send Query to UPS: ?POWERSTAT<CR>
Action: Power status messages will be returned
Response: Normal operation
$PWR = NORMAL<CR>
Overvoltage $PWR = OVERVOLTAGE<CR>
Undervoltage $PWR = UNDERVOLTAGE<CR>
Lost Power $PWR = LOST POWER<CR>
Test Mode $PWR = TEST<CR>
POWER
Requests the input and output voltages.
Send Query to UPS: ?POWER<CR>
Action: Voltage status messages will be displayed
Response: $VOLTS_IN = vvv<CR>
$VOLTS_OUT = vvv<CR>
$WATTS = xxxx<CR>
$VA = xxxx<CR>
(xxx is expressed in decimal format)
If the value is less than 100, the hundreds digit is represented with a 0. For example a line voltage of 92VAC would be expressed
as: $VOLTAGE = 092<CR>
LOAD LEVEL STATUS
Requests the load level, expressed as percentage of maximum.
Send Query to UPS: ?LOADSTAT<CR>
Action: Load level will be displayed
Response: $LOAD = xxx<CR>
(xxx is the load level (percentage of maximum load) expressed in decimal format)
If the value is less than 100, the hundreds digit is represented with a 0.
BATTERY LEVEL STATUS
Requests the battery level, expressed as a percentage of maximum (full charge).
15