"Prg" Menu parameters list:
"Prg" Menu parameters list: 1 - 2
Menù
Par Label Description
label
200
SEtC Room set point in cooling mode (Comfort temperature)
201
AttC Attenuation value on Room set point in cooling mode
202
SEtH Room set point in heating mode (Comfort temperature)
203
AttH Attenuation value on Room set point in heating mode
Comfort/Attenuation conditions change:
204
C-A
On: Change comfort / Attenuation bands
Off: Time Zones of Comfort / Attenuation disabled (manual override)
Comfort conditions period start:
205
StC
Time of day at which the transition is forced to the conditions of Time
of day at which the transition is forced to the conditions of Comfort
Comfort conditions period end:
206
EnC
Time of day in which it is forced passage conditions Attenuation
Differential on Room temperature set point
207
diFF
Differential on the set temperature in heating / cooling, with which you
start the heat pump
208 SAMb Active room set point
Voltage output state Room Termostat (clamp C-D):
209
tHEr
210 E1Mn Winter climatic curve, minimum external environment set temperature
Winter climatic curve, maximum external environment set
211 E1MA
temperature
212
t1Mn Winter climatic curve (radiant), minimum outlet water temperature set
213
t1MA Winter climatic curve (radiant), maximum outlet water temperature set
USYS
Multiplier of the difference, between the set room temperature, and
214
ty1
the measured one, that represents the dynamic compensation of the
temperature curve winter. If the KCTR is not connected, or in case of
alarm AMBT, such compensation is not active
Winter heating curve (fan coils), set outlet water temperature
215
t2Mn
minimum (active when remote contact "Set point 2" closed)
Winter heating curve (fan coils), set outlet water temperature
216
t2MA
maximum (active when remote contact "Set point 2" closed)
217 E3Mn Heating curve summer, set minimum outdoor temperature
218 E3MA Heating curve summer, set the maximum external temperature
Summer temperature curve (radiant), set outlet water temperature
219
t3Mn
minimum
Summer temperature curve (radiant), set outlet water temperature
220
t3MA
maximum
Summer temperature curve (radiating), dynamic compensation
Multiplier of the difference, between the set room temperature, and
221
dy3
the measured one, that represents the dynamic compensation of the
temperature curve winter. If the KCTR is not connected, or in case of
alarm AMBT, such compensation is not active
t4Mn Summer temperature curve (fan coils), set outlet water temperature
222
minimum (active when remote contact "Set point 2" closed)
Summer temperature curve (fan coils), set outlet water temperature
223
t4Ma
maximum (active when remote contact "Set point 2" closed)
224
tMa
Maximum temperature hot water radiant plant
Section I :: User
X=Parameter also available on KCTR
73
U.
Range
Default KCTR PW Address
min
max
m.
°C
15
30
24
°C
1
10
6
°C
5
30
20
°C
1
10
4
-
Off
On
Off
h:
00:00 EnC
08:00
min
h:
StC
23:59
21:00
min
°C
1
5
1
Read
°C
-
-
value
Read
-
On
Off
value
°C
-20
5
-5
°C
10
40
20
°C
10
60
22
°C
20
60
45
-
0
9
0
°C
20
60
45
°C
10
60
45
°C
20
40
23
°C
20
40
32
°C
5
25
15
°C
5
25
22
-
0
9
0
°C
5
25
7
°C
5
25
7
°C
10
60
45
S = Password service (48)
EN
X
16413
X
16415
X
16414
X
16416
X
16417
X
16466
X
16467
S
16418
8984
8986
S
16419
S
16420
S
16421
S
16422
S
16423
S
16424
S
16425
S
16426
S
16427
S
16428
S
16429
S
16430
S
16431
S
16432
16433
Tabla de contenido
loading

Este manual también es adecuado para:

Electa thaity 105Electa thaity 110Electa thaity 116

Tabla de contenido