EN
Menu parameters list "Set" 2-2
Menù
Par Label Description
label
State of input "Setpoint 2" (terminals 13-14)
On: Contact closed. Required to produce water at temperatures
114 FAnC
necessary for the operation of the fan coil.
Off: Open contact. Production of water at the temperature required to
operate the only radiating system.
Input Status "Night mode" (terminals 9-10)
On: Contact closed. Limitation maximum working frequency of the
115
nigt
compressor
di
Off: Open contact. No limitations on frequency
Input Status "Remote Cool / Heat" (terminals 11-12)
116
On: Contact closed. See setting par. 101 "MOdE"
COOL
Off: Open contact. See setting par. 101 "MOdE"
State external contact "Remote On / Off"
On: Contact closed. Enable controls on / off of USER INTERFACE
117 OnOF
(KCTR and if installed)
Off: Open contact. Activate only the function of antifreeze
119 S rH Room humidity set point (active only with KCTR installed)
dEHU
Differential on room humidity set point (active only with KCTR
120 d rH
installed)
DHW Production:
122 ESAn
On: Enabled
Off: Not enabled
DHW Control:
0: Control through NTC probe
1: closed contact = DHW requested (through thermostat in the
123 COnt
storage domestic hot water),
2: open contact = DHW requested (through thermostat in the storage
domestic hot water)
Beginning of period DHW priority:
124 OnP
Now a day on which the production of domestic hot water has priority
over climate
End of the period DHW priority:
125 OFFP
Time of the day to which the production of domestic hot water has
priority over climate
SAni
126 SEtS DHW Set point (storage domestic hot water)
127 diFS Differential on DHW Set point (storage domestic hot water)
128 tUSA Heat pump water delivery set point for DHW production
Voltage output state W.V.Sanitary (clamp H):
129 3UAY
On: H-N=230 V
Off: H-N=0 V
DHW production circulator delay
130 dELP
Activation delay time of pump 1, respect to activation of the output
W.V.Sanitary
DHW production integrated electric heater delay
Delay time from beginning of DHW production with HP, where the
131 dELE
DHW electric heater is activates, as support for reaching the set
point.
If set = 0 function disabled
132 SEtE DHW production integrated electric heater set point
Section I :: User
U.m.
min
min
min
min
X=Parameter also available on KCTR
70
Range
Default KCTR
min
max
Read
-
-
-
value
Read
-
-
-
value
Read
-
-
-
value
Read
-
-
-
value
%
30
90
60
%
1
20
5
-
Off
On
On
-
0,1,2
1
h:
00:00 23:59 00:00
h:
00:00 23:59 23:59
° C
10
60
50
° C
1
15
5
° C
SEtS
60
55
Read
-
-
-
value
0
9
0
0
120
0
° C
10
70
50
S = Password service (48)
PW
Address
8963
8962
8966
8965
X
16392
S
16393
X
16395
S
16396
S
16397
S
16398
16399
S
16400
16401
8979
S
16402
S
16403
S
16404