Table 10 – Input Signal, Power and Display Specifications
Power Supply
Compliance Voltage Rating
Minimum Current Signal to Start Up
Minimum Input Span for Split Range
Operation
Upper Range Value for Split Range Operation
Lower Range Value for Split Range Operation
Minimum/Maximum Wire Size
Strip Length
DIgital Communication
Local Display Liquid Crystal (optional)
Push Buttons
Table 11 - Construction Material Specifications
Housing and Cover
Weight
Relay and Manifold
I/P Motor
Mounting Bracket
Magnet Holder
Pole Ring
Levers
Taken from 4 - 20 mA control signal
9.0 V at 20 mA, 11.0 V at 4.0 mA
3.2 mA
5 mA
Between 8 and 20 mA
Between 4 and 14 mA
28/14 AWG
0.22 in / 6 mm
HART Communication protocol signal from
ValVue software on a personal computer or a
hand held device. HART point to point and burst
mode.
Three lines of nine alpha numeric characters
Three push buttons
Aluminum ASTM B85 SC84B standard
Standard - 5.8 lbs./ 2.63 kg
PPS, 300 Series Stainless Steel, nitrile diaphragms
430 Stainless Steel, PPS, 300 Series Stainless Steel
300 Series Stainless Steel
Corrosion Protected Anodized Aluminum 6061 T6
416 Stainless Steel
300 Series Stainless Steel
A-3