Especificaciones
Físicas y Operaciones
Operating Temperature Limits
Storage Temperature Limits
Temperature Effect
Supply Pressure Effect
Relative Humidity
Humidity Effect
Insulation Resistance
MTBF
Electromagnetic Compatibility
Electrostatic
Fast Transient Burst
Vibration Influence
Measured at SVI II Housing
Magnetic Field Influence
Especificaciones
Esta sección provee las especificaciones físicas y operacionales del
SVI II AP.
Table 8
Environmental Specifications
-58 deg. F to 185 deg. F (-50 deg. C to 85 deg. C)
-58 deg. F to 200 deg. F (-50 deg. C to 93 deg. C)
< 0.005% / deg. F typical; -40 deg. F to 180 deg. F
(< 0.01% / deg. C typical; -40 deg. C to 82 deg. C)
0.05% per psi (.73% per bar)
10 to 90% non-condensing
Less than 0.2% after 2 days at 104 F (40 deg. C),
95% Relative Humidity.
Greater than 10 G Ohms at 50% RH.
49 years based on MIL handbook calculation for
electronic parts and field data on mechanical parts
Electrostatic discharge — No effect with contact
discharge level of 4KV and air discharge level of 8 KV
(IEC 1000-4-2)
Radio frequency interference — Less than 0.2% at 10
volts per meter (EN 50140)
No effect at 2 KV (Coupling clamp IEC 1000-4-4).
4 mm at 5 - 15 Hz - Negligible
2 G at 15 - 150 Hz Less than 2 % of span
1 G at 150 - 2000 Hz - Less than 2 % of span
Negligible at 30 A/m (EN61000-4-8)
CE MARK certified to EN50081-2 and EN50082-2