8 Diagnosis, asset management and service
Maintenance
Code
Cause
Text mes-
sage
M500
The data could
not be restored
Error during
during the reset to
the reset "de-
delivery status
livery status"
M501
Hardware error
EEPROM
Error in the
non-active li-
nearisation
table
M502
Hardware error
EEPROM
Error in the
diagnostics
memory
M503
The echo/noise
ratio is too small
Measu-
for reliable measu-
rement
rement
reliability too
low
M504
Hardware defect
Error at a
device inter-
face
M505
Level echo can
no longer be de-
No echo
tected
available
8.4

Rectify faults

Reaction when malfunction occurs
The operator of the system is responsible for
taking suitable measures to rectify faults.
Fault rectification
The first measures are:
Evaluation of fault messages
Checking the output signal
Treatment of measurement errors
A smartphone/tablet with the VEGA Tools app or
a PC/notebook with the software PACTware and
the suitable DTM offer you further comprehen-
sive diagnostic possibilities. In many cases, the
causes can be determined in this way and the
32
faults eliminated.
Rectification
4 ... 20 mA signal
Connect a multimeter in the suitable measuring
range according to the wiring plan. The following
table describes possible errors in the current
Repeat reset
signal and helps to eliminate them:
Load XML file with
sensor data into
the sensor
Send instrument
for repair
Send instrument
for repair
Check installation
and process con-
ditions
Clean the antenna
Change polarisati-
on direction
Check connec-
tions
Reaction after fault rectification
Send instrument
for repair
Depending on the reason for the fault and the
measures taken, the steps described in chapter
Clean the antenna
"Setup" must be carried out again or must be
Remove possible
checked for plausibility and completeness.
false echoes
Optimize sensor
24 hour service hotline
position and ori-
Should these measures not be successful,
entation
please call in urgent cases the VEGA service
hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal
working hours, seven days a week around the
clock.
Since we offer this service worldwide, the
support is provided in English. The service itself
is free of charge, the only costs involved are the
normal call charges.
8.5
You can find an instrument return form as
well as detailed information about the proce-
dure in the download area of our homepage:
www.vega.com. By doing this you help us carry
out the repair quickly and without having to call
Error
Cause
4 ... 20 mA
Fluctuating mea-
signal not
sured value
stable
4 ... 20 mA
Electrical connec-
signal mis-
tion faulty
sing
Voltage supply
missing
Operating voltage
too low, load resis-
tance too high
Current sig-
Sensor electro-
nal greater
nics defective
than 22 mA,
less than
3.6 mA
How to proceed if a repair is
necessary
VEGAPULS WL S 61 • 4 ... 20 mA
Rectification
Set damping
Check connec-
tion, correct, if
necessary
Check cables for
breaks; repair if
necessary
Check, adapt if
necessary
Replace device or
send in for repair
depending on de-
vice version